Measuring No - Load and Load noise of Power Transformers using the Sound Pressure and Sound Intensity Methods - Part - I: Outdoors measurements

被引:0
作者
Girgis, Ramsis S. [1 ]
Garner, Keith [1 ]
Bernesjoe, Mats [1 ]
Anger, Jan [2 ]
机构
[1] ABB Power Transformers, St Louis, MO USA
[2] ABB Power Transformers, Ludvika, Sweden
来源
2008 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-11 | 2008年
关键词
Power Transformers; Transformer Noise; Sound Power Measurement; Sound Intensity; Sound Power;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The subject of deciding on the most appropriate method of determining the true sound power level of a power transformer has been discussed through the transformer industry for decades. It is the objective of this 2 - Part paper to identify magnitudes of the contributions to the inherent difference in power transformer noise level measurements when using the Sound Pressure method versus when using the Sound Intensity method. The paper presents results of comprehensive outdoors and indoors measurements made of the frequency spectrum and total noise of a large number of power transformers using the two measuring methods. In Part - I of the paper, results of the outdoor measurements made on the total noise produced by three power transformers in low ambient / no sound reflections locations are presented. Results of the indoors measurements made on 48 power transformers of 12 - 336 WA power ratings are presented in Part - II of the paper. Appropriate conditions for accurate indoors measurement of transformer noise when using the Sound Intensity method have been derived. Modifications to the existing IEC and IEEE Industry Standards of transformer noise testing are proposed.
引用
收藏
页码:2671 / +
页数:3
相关论文
共 8 条
  • [1] BAKKERS W, CIGRE SESS 1988
  • [2] APPLICATION OF THE INTENSITY TECHNIQUE TO THE CHARACTERIZATION OF TRANSFORMER NOISE
    CHAMPOUX, Y
    GOSSELIN, B
    NICOLAS, J
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) : 1802 - 1808
  • [3] *IEC, 600761012005 IEC
  • [4] IEC, 60076102001 IEC
  • [5] IEEE, C5712902006 IEEE
  • [6] VALIDATION OF ACOUSTIC INTENSITY MEASUREMENTS FOR POWER TRANSFORMERS
    KENDIG, RP
    WRIGHT, SE
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (04) : 1524 - 1530
  • [7] REIPLINGER E, CIGRE SESS 1988
  • [8] *STUD COMM 12 CIGR, 1992, 144 STUD COMM 12 CIG