Design and characterization of a cylindrical, water-cooled heat sink for thermoelectric air-conditioners

被引:31
作者
Riffat, SB [1 ]
Qiu, GQ [1 ]
机构
[1] Univ Nottingham, Sch Built Environm, Inst Sustainable Energy & Technol, Nottingham NG7 2RD, England
关键词
thermoelectric air-conditioner (TEACs); heat sink; water-cooled; overall heat transfer rate; overall thermal resistance; COP;
D O I
10.1002/er.1124
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Thermoelectric air-conditioners (TEACs) are becoming much concerned due to their many advantages, but the low COPs limit their broad applications. The two key factors to raise the CON of TEACs are both the improvement of thermoelectric materials and the optimum design of hot side heat sinks. This paper provides a thermoelectric air-conditioning system with a water-cooled sleeve heat sink in the hot side of the thermoelectric pellets, and compares the overall heat transfer rates q(L), the total heat resistances R-t between the water-cooled and air-cooled heat sinks as well as the optimum fin length, the optimum fluid flow velocity and the optimum fin gap distance. The simulation results show that the overall heat transfer rate of water-cooled heat sink is more than 20 times that of air-cooled heat sink under the other same circumstances, as a result of the improvement of heat sink.. the optimum COP of the thermoelectric air-conditioning system with the water-cooled heat sink proximately doubles that with the air-cooled heat sink. This novel system could be simply installed and applied all the year round for cooling in summer and heating in winter. Copyright (c) 2005 John Wiley & Sons, Ltd.
引用
收藏
页码:67 / 80
页数:14
相关论文
共 7 条
[1]   Increase of COP in the thermoelectric refrigeration by the optimization of heat dissipation [J].
Astrain, D ;
Vián, JG ;
Domínguez, M .
APPLIED THERMAL ENGINEERING, 2003, 23 (17) :2183-2200
[2]  
Ioffe A.F., 1958, SEMICONDUCTOR THERMO
[3]   Experimentation of a novel thermoelectric heat pump system [J].
Riffat, S.B. ;
Ma, X. ;
Qiu, G. .
International Journal of Ambient Energy, 2004, 25 (04) :177-186
[4]   Comparative investigation of thermoelectric air-conditioners versus vapour compression and absorption air-conditioners [J].
Riffat, SB ;
Qiu, GQ .
APPLIED THERMAL ENGINEERING, 2004, 24 (14-15) :1979-1993
[5]   Mathematic simulation on thermoelectric power generation with cylindrical multi-tubes [J].
Suzuki, RO ;
Tanaka, D .
JOURNAL OF POWER SOURCES, 2003, 124 (01) :293-298
[6]   Mathematical simulation of thermoelectric power generation with the multi-panels [J].
Suzuki, RO ;
Tanaka, D .
JOURNAL OF POWER SOURCES, 2003, 122 (02) :201-209
[7]   Advanced heat exchange technology for thermoelectric cooling devices [J].
Webb, RL ;
Gilley, MD ;
Zarnescu, V .
JOURNAL OF ELECTRONIC PACKAGING, 1998, 120 (01) :98-105