CFD modelling of aerodynamic sealing by vertical and horizontal air curtains

被引:49
作者
Goncalves, J. C. [1 ,2 ]
Costa, J. J. [2 ]
Figueiredo, A. R. [2 ]
Lopes, A. M. G. [2 ]
机构
[1] ESAV, Inst Politecn Viseu Quinta Alagoa, Ctr Estudos Educ Tecnol & Saude, P-3500606 Viseu, Portugal
[2] Univ Coimbra, Dep Eng Mecan, ADAI LAETA, P-3030788 Coimbra, Portugal
关键词
Air curtain; CFD; Heat transfer; Refrigerated room; Energy consumption; REFRIGERATED DISPLAY CABINETS; COLD ROOM INFILTRATION; ENERGY SAVINGS; SIMULATION; DEVICES;
D O I
10.1016/j.enbuild.2012.06.007
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This work presents a comparative study of the aerodynamic sealing of doorways of refrigerated rooms, obtained by vertical and horizontal air curtain devices (ACD). The sealing efficiency is estimated for different situations, with the ACD installed inside, outside or on both sides of the door. For this purpose, a numerical model was developed for the simulation of the turbulent non-isothermal 3D airflow generated by the air curtain in the transient period after the door is opened. The buoyancy-induced airflow field when the ACD is turned off and the door is open was taken as a reference to assess the sealing efficiency. Numerical results are plausible and comply with the physical interpretation of the convective phenomena. In line with previous investigations, the optimum velocity of the air jet was found, corresponding to the highest sealing effect. The advantage of installing the ACD outside the refrigerated room was shown by the present simulations. According to the present study, downward blowing air curtains present better sealing efficiency (over 70%) compared to horizontal jet air curtains (about 55%). Although the direct air recirculation provides a better sealing efficiency (over 80%), the system complexity and the installation and maintenance costs inhibit its common use. (C) 2012 Elsevier B.V. All rights reserved.
引用
收藏
页码:153 / 160
页数:8
相关论文
共 27 条
  • [1] CFD simulation of refrigerated display cabinets
    Cortella, G
    Manzan, M
    Comini, G
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2001, 24 (03): : 250 - 260
  • [2] Energy savings by aerodynamic sealing with a downward-blowing plane air curtain - A numerical approach
    Costa, J. J.
    Oliveira, L. A.
    Silva, M. C. G.
    [J]. ENERGY AND BUILDINGS, 2006, 38 (10) : 1182 - 1193
  • [3] Two- and three-dimensional CFD applied to vertical display cabinets simulation
    D'Agaro, P
    Cortella, G
    Croce, G
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2006, 29 (02): : 178 - 190
  • [4] DOWNING CC, 1993, ASHRAE TRAN, V99, P356
  • [5] Three-dimensional effects of an air curtain used to restrict cold room infiltration
    Foster, A. M.
    Swain, M. J.
    Barrett, R.
    D'Agaro, P.
    Ketteringham, L. P.
    James, S. J.
    [J]. APPLIED MATHEMATICAL MODELLING, 2007, 31 (06) : 1109 - 1123
  • [6] Effectiveness and optimum jet velocity for a plane jet air curtain used to restrict cold room infiltration
    Foster, A. M.
    Swain, M. J.
    Barrett, R.
    D'Agaro, P.
    James, S. J.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2006, 29 (05): : 692 - 699
  • [7] Gaspar P.D., 2003, Proc. VI Congresso Ibero-Americano de Engenharia Mecanica (CIBEM6), V1, P687
  • [8] Simulation of the performance of single jet air curtains for vertical refrigerated display cabinets
    Ge, YT
    Tassou, SA
    [J]. APPLIED THERMAL ENGINEERING, 2001, 21 (02) : 201 - 219
  • [9] Goncalves J.C., 2009, P 3 C NAC MEC FLUID
  • [10] Goncalves J.C., 2009, P 5 C IB 3 C IB CIEN