A simple dynamic model of cooling coil unit

被引:55
作者
Jin, GY
Cai, WH
Wang, YW
Yao, Y
机构
[1] Nanyang Technol Univ, Sch Elect & Elect Engn, Singapore 639798, Singapore
[2] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200330, Peoples R China
关键词
heating; ventilation and air conditioning system; cooling coil unit; air handling unit; engineering model; mass and energy balance; dynamic modeling; experiments;
D O I
10.1016/j.enconman.2005.10.020
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper, a dynamic cooling coil unit (CCU) model is developed by extending the CCU engineering model and by combining the model with the mass and energy balance equations. Commissioning information is then used to estimate, at most, six model parameters by a nonlinear on line identification method. Unlike other existing dynamic CCU models for control and optimization, this modeling method is relatively simple and exactly captures the nonlinear characteristics over a wide operating range of the CCU without requiring geometric specifications, which is very convenient in real time engineering control practice. Experiments on a centralized heating, ventilation and air conditioning (HVAC) pilot plant are conducted to show that the method is robust and gives an accurate match to real performance over the wide range of operating conditions. This method is expected to work well for real time control of an operating HVAC system. Even more, the modeling methodology can also be extended to other heat exchangers. (c) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2659 / 2672
页数:14
相关论文
共 18 条
[1]   Robust identification of first-order plus dead-time model from step response [J].
Bi, Q ;
Cai, WJ ;
Lee, EL ;
Wang, QG ;
Hang, CC ;
Zhang, Y .
CONTROL ENGINEERING PRACTICE, 1999, 7 (01) :71-77
[2]   Advanced controller auto-tuning and its application in HVAC systems [J].
Bi, Q ;
Cai, WJ ;
Wang, QG ;
Hang, CC ;
Lee, EL ;
Sun, Y ;
Liu, KD ;
Zhang, Y ;
Zou, B .
CONTROL ENGINEERING PRACTICE, 2000, 8 (06) :633-644
[3]  
BOCANEGRA LM, 1992, ASME WINT ANN M NOV
[4]  
GARTNER JR, 1969, ASHRAE T, V75, P53
[5]   THE TRANSIENT-RESPONSE OF FINNED CROSS-FLOW HEAT-EXCHANGERS [J].
KABELAC, S .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1989, 32 (06) :1183-1189
[6]  
Khan A.Y., 1994, ASHRAE T, V100, P54
[7]  
Kreith F., 1997, CRC HDB ENERGY EFFIC
[8]  
Lebrun J., 1990, P SYST SIM BUILD 90
[9]   Global optimization for overall HVAC systems - Part II problem solution and simulations [J].
Lu, L ;
Cai, WJ ;
Soh, YC ;
Xie, LH .
ENERGY CONVERSION AND MANAGEMENT, 2005, 46 (7-8) :1015-1028
[10]  
Lu L, 2005, ENERG BUILDINGS, V37, P11, DOI 10.1016/j.enbuiId.2003.12.007