Sustainable Monitoring of Indoor Air Pollutants in an Underground Subway Environment Using Self-Validating Soft Sensors

被引:18
|
作者
Liu, Hongbin [1 ]
Kang, OnYu [1 ]
Kim, MinJeong [1 ]
Oh, TaeSeok [1 ]
Lee, SeungChul [1 ]
Kim, Jeong Tai [2 ]
Yoo, ChangKyoo [1 ]
机构
[1] Kyung Hee Univ, Dept Environm Sci & Engn, Coll Engn, Ctr Environm Studies, Yongin 446701, South Korea
[2] Kyung Hee Univ, Dept Architectural Engn, Coll Engn, Yongin 446701, South Korea
基金
新加坡国家研究基金会;
关键词
Fault detection; Indoor air quality; Reconstruction-based simulation; Sensor validation; Recursive partial least squares; Self-validating soft sensor; Subway system; FAULT-DETECTION; QUALITY; RECONSTRUCTION; IDENTIFICATION; DIAGNOSIS; MODEL; ALGORITHMS; PREDICTION; TOOL;
D O I
10.1177/1420326X12469744
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The purpose of this study is to develop a self-validating soft sensor to improve the prediction performance of indoor air quality soft sensors in an underground subway station. The reconstruction-based self-validation method was proposed and implemented in order to: (1) determine the optimal number of principal components when building a principal component analysis training model, (2) enhance the diagnosis accuracy when identifying faulty sensors and (3) reconstruct faulty measurements in a straightforward manner. Two soft sensors based on partial least squares and recursive partial least squares models were developed and their prediction performance was compared in the cases of using faulty sensor measurements and using reconstructed sensor values. Two types of sensor faults including a bias fault and a drifting fault were evaluated using the proposed method. The monitoring results show that the developed sensor self-validation strategy has a powerful ability to correctly detect, identify and reconstruct the sensor faults in the subway system. In addition, the proposed self-validation soft sensing technique could achieve sustainable monitoring of indoor air pollutants in the underground subway environment, because the reconstructed values can be used to replace the measured data when sensor faults have been detected by the detection indices.
引用
收藏
页码:94 / 109
页数:16
相关论文
共 21 条
  • [1] An integral approach to inferential quality control with self-validating soft-sensors
    Godoy, Jose L.
    Marchetti, Jacinto L.
    Vega, Jorge R.
    JOURNAL OF PROCESS CONTROL, 2017, 50 : 56 - 65
  • [2] Development of Self-Validating Soft Sensors Using Fast Moving Window Partial Least Squares
    Liu, Jialin
    Chen, Ding-Sou
    Shen, Jui-Fu
    INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2010, 49 (22) : 11530 - 11546
  • [3] Multivariate statistical monitoring of subway indoor air quality using dynamic concurrent partial least squares
    Liu, Hongbin
    Yang, Chong
    Huang, Mingzhi
    Yoo, ChangKyoo
    ENVIRONMENTAL SCIENCE AND POLLUTION RESEARCH, 2020, 27 (04) : 4159 - 4169
  • [4] Effect of platform screen doors on the indoor air environment of an underground subway station
    Han, Hwataik
    Lee, Jun-Yong
    Jang, Kyung-Jin
    INDOOR AND BUILT ENVIRONMENT, 2015, 24 (05) : 672 - 681
  • [5] Multivariate statistical monitoring of subway indoor air quality using dynamic concurrent partial least squares
    Hongbin Liu
    Chong Yang
    Mingzhi Huang
    ChangKyoo Yoo
    Environmental Science and Pollution Research, 2020, 27 : 4159 - 4169
  • [6] Air Pollution Monitoring and Control System for Subway Stations Using Environmental Sensors
    Kim, Gyu-Sik
    Son, Youn-Suk
    Lee, Jai-Hyo
    Kim, In-Won
    Kim, Jo-Chun
    Oh, Joon-Tae
    Kim, Hiesik
    JOURNAL OF SENSORS, 2016, 2016
  • [7] Online monitoring and interpretation of periodic diurnal and seasonal variations of indoor air pollutants in a subway station using parallel factor analysis (PARAFAC)
    Lee, SeungChul
    Liu, Hongbin
    Kim, MinJeong
    Kim, Jeong Tai
    Yoo, ChangKyoo
    ENERGY AND BUILDINGS, 2014, 68 : 87 - 98
  • [8] Sustainable subway indoor air quality monitoring and fault-tolerant ventilation control using a sparse autoencoder-driven sensor self-validation
    Loy-Benitez, Jorge
    Li, Qian
    Nam, KiJeon
    Yoo, ChangKyoo
    SUSTAINABLE CITIES AND SOCIETY, 2020, 52
  • [9] Analysis and prediction of indoor air pollutants in a subway station using a new key variable selection method
    Lim, JungJin
    Kim, YongSu
    Oh, TaeSuk
    Kim, MinJung
    Kang, OnYu
    Kim, Jeong Tai
    Kim, In-Won
    Kim, Jo-Chun
    Jeon, Jae-Sik
    Yoo, ChangKyoo
    KOREAN JOURNAL OF CHEMICAL ENGINEERING, 2012, 29 (08) : 994 - 1003
  • [10] A real-time monitoring and assessment method for calculation of total amounts of indoor air pollutants emitted in subway stations
    Oh, TaeSeok
    Kim, MinJeong
    Lim, JungJin
    Kang, OnYu
    Shetty, K. Vidya
    SankaraRao, B.
    Yoo, ChangKyoo
    Park, Jae Hyung
    Kim, Jeong Tai
    JOURNAL OF THE AIR & WASTE MANAGEMENT ASSOCIATION, 2012, 62 (05) : 517 - 526