Selection Criteria for Oil Transformer Measurements to Calculate the Health Index

被引:18
作者
Ibrahim, K. [1 ]
Sharkawy, R. M. [1 ]
Temraz, H. K. [2 ]
Salama, M. M. A. [3 ]
机构
[1] Arab Acad Sci & Technol & Maritime Transport, Dept Elect & Control Engn, Cairo, Egypt
[2] Ain Shams Univ, Dept Elect Power & Machines Engn, Cairo, Egypt
[3] Univ Waterloo, Dept Elect & Comp Engn, Waterloo, ON, Canada
关键词
Asset management; condition monitoring; oil insulation; insulation testing; support vector machines; optimization;
D O I
10.1109/TDEI.2016.006058
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, a study of the effect of a group of transformer measurements on Health Index (HI) calculation is presented. Different methodologies for selecting the most efficient group of diagnostic measurements used in classifying transformer HI are investigated. A Binary Cat Swarm Optimization (BCSO) technique is undertaken based on Support Vector Machines (SVM). The technique depends on selecting the optimal parameters for SVM. The effect of selecting HI classes as well as class's boundaries is also studied. The measurements of fourteen diagnostic transformer tests, including the furan analysis, dissolved gas analysis, and further oil analysis for 724 distribution transformers are studied, and the corresponding HI is calculated according to industrial standards. The model renders the best-selected group of measurements that assist in the formulation of the health index with minimum error and high confidence.
引用
收藏
页码:3397 / 3404
页数:8
相关论文
共 30 条
[1]  
Abu-Elanien AEB, 2011, INT S INNOVATIONS IN, V2011, P1
[2]   Calculation of a Health Index for Oil-Immersed Transformers Rated Under 69 kV Using Fuzzy Logic [J].
Abu-Elanien, Ahmed E. B. ;
Salama, M. M. A. ;
Ibrahim, M. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (04) :2029-2036
[3]  
Anders G., 2006, POWER ENG SOC GEN M, P1
[4]  
[Anonymous], 2006, IEEE STD C57106 2006, P1, DOI DOI 10.1109/IEEESTD.2006.99501
[5]  
[Anonymous], 2003, FACILITIES INSTRUCTI
[6]  
[Anonymous], 2014, P INT C ENG TECHN IC
[7]  
[Anonymous], 7 INT C UB MED COMP
[8]  
[Anonymous], 2009, P 41 N AM POWER S
[9]  
[Anonymous], 8 INT S ADV TOP EL E
[10]  
[Anonymous], TRANSF MAINT FAC INS