Thermodynamic analysis of an absorption refrigeration system with ionic-liquid/refrigerant mixture as a working fluid

被引:139
作者
Kim, Yoon Jo [1 ]
Kim, Sarah [2 ]
Joshi, Yogendra K. [3 ]
Fedorov, Andrei G. [3 ]
Kohl, Paul A. [2 ]
机构
[1] Washington State Univ Vancouver, Dept Mech Engn, Vancouver, WA 98686 USA
[2] Georgia Inst Technol, Sch Chem & Biomol Engn, Atlanta, GA 30332 USA
[3] Georgia Inst Technol, George W Woodruff Sch Mech Engn, Atlanta, GA 30332 USA
关键词
Ionic liquid; Absorption system; Waste-heat; Electronics cooling; LIQUID-EQUILIBRIA; SOLUBILITY; SOLVENTS; DESIGN;
D O I
10.1016/j.energy.2012.04.048
中图分类号
O414.1 [热力学];
学科分类号
摘要
Thermodynamics of an ionic-liquid (IL) based absorption refrigeration system has been numerically analyzed. It provides an alternative to the normally toxic working fluids, such as the ammonia in conventional absorption systems. The use of ILs also eliminates crystallization and metal-compatibility problems of the water/LiBr system. Mixtures of refrigerants and imidazolium-based ILs are theoretically explored as the working fluid pairs in a miniature absorption refrigeration system, so as to utilize waste-heat to power a refrigeration/heat pump system for electronics cooling. A non-random two-liquid (NRTL) model was built and used to predict the solubility of the mixtures. Saturation temperatures at the evaporator and condenser were set at 25 degrees C and 50 degrees C, respectively, with the power dissipation of 100 W. Water in combination with [emim][BF4] (1-ethyl-3-methylimidazolium tetrafluoroborate) gave the highest coefficient of performance (COP) around 0.9. The refrigerant/IL compatibility indicated by the circulation ratio, alkyl chain length of the IL, and thermodynamic properties of the refrigerants, such as latent heat of evaporation were proven to be important factors in determining the performance of the absorption system. The negative effect of high viscosity was mitigated by dilution of the IL with the refrigerant and the use of slightly larger microfluidic channel heat exchangers. (C) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1005 / 1016
页数:12
相关论文
共 60 条
  • [21] High-pressure volumetric properties of imidazolium-based ionic liquids: Effect of the anion
    Jacquemin, Johan
    Husson, Pascale
    Mayer, Vladimir
    Cibulka, Ivan
    [J]. JOURNAL OF CHEMICAL AND ENGINEERING DATA, 2007, 52 (06) : 2204 - 2211
  • [22] How hazardous are ionic liquids?: Structure-activity relationships and biological testing as important elements for sustainability evaluation
    Jastorff, B
    Störmann, R
    Ranke, J
    Mölter, K
    Stock, F
    Oberheitmann, B
    Hoffmann, W
    Hoffmann, J
    Nüchter, M
    Ondruschka, B
    Filser, J
    [J]. GREEN CHEMISTRY, 2003, 5 (02) : 136 - 142
  • [23] Closed-loop electroosmotic microchannel cooling system for VLSI circuits
    Jiang, LN
    Mikkelsen, J
    Koo, JM
    Huber, D
    Yao, SH
    Zhang, L
    Zhou, P
    Maveety, JG
    Prasher, R
    Santiago, JG
    Kenny, TW
    Goodson, KE
    [J]. IEEE TRANSACTIONS ON COMPONENTS AND PACKAGING TECHNOLOGIES, 2002, 25 (03): : 347 - 355
  • [24] Measurement and correlation of vapor-liquid equilibria of binary systems containing the ionic liquids [EMIM] [(CF3SO2)2N], [BMIM] [(CF3SO2)2N], [MMIM] [(CH3)2PO4] and oxygenated organic compounds respectively water
    Kato, R
    Gmehling, J
    [J]. FLUID PHASE EQUILIBRIA, 2005, 231 (01) : 38 - 43
  • [25] Temperature Dependence of the Solubility of Carbon Dioxide in Imidazolium-Based Ionic Liquids
    Kerle, Daniela
    Ludwig, Ralf
    Geiger, Alfons
    Paschek, Dietmar
    [J]. JOURNAL OF PHYSICAL CHEMISTRY B, 2009, 113 (38) : 12727 - 12735
  • [26] Kim S, APPL ENERGY UNPUB
  • [27] Kim YJ, 2011, P 5 INT C EN SUST 20
  • [28] An absorption based miniature heat pump system for electronics cooling
    Kim, Yoon Jo
    Joshi, Yogendra K.
    Fedorou, Andrei G.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (01): : 23 - 33
  • [29] Diol-Functionalized Imidazolium-Based Room-Temperature Ionic Liquids with Bis(trifluoromethanesulfonimide) Anions that Exhibit Variable Water Miscibility
    LaFrate, Andrew L.
    Bara, Jason E.
    Gin, Douglas L.
    Noble, Richard D.
    [J]. INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2009, 48 (18) : 8757 - 8759
  • [30] Two-phase flow in high-heat-flux micro-channel heat sink for refrigeration cooling applications: Part I - pressure drop characteristics
    Lee, J
    Mudawar, I
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2005, 48 (05) : 928 - 940