Wind farm node connected DFIG/back-to-back converter coupling transient model for grid integration studies

被引:8
作者
Ostolaza, J. X. [1 ]
Etxeberria, A. [1 ,3 ]
Zubia, I. [2 ]
机构
[1] Univ Basque Country UPV EHU, Syst Engn & Control Dept, Donostia San Sebastian 20018, Spain
[2] Univ Basque Country UPV EHU, Dept Elect Engn, Donostia San Sebastian 20018, Spain
[3] ESTIA, F-64210 Bidart, France
关键词
Wind power generation; DFIG wind generator full-order transient model; Wind farm node Thevenin impedance; Grid and rotor side converter multi-loop control; Decoupling control; Operational modes of the generator; OF-THE-ART; TURBINE; SYSTEMS; DESIGN;
D O I
10.1016/j.enconman.2015.09.063
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents the explicit electromagnetic transient model of a Doubly Fed Induction Generator (DFIG), that includes its coupling with the back-to-back converter, when the generator/converter set is connected to the wind farm's Thevenin equivalent, as seen from DFIG's terminals. Besides that, DFIG's grid side converter control system is defined in detail, so that expressions for the direct tuning of all compensators are provided. The overall electromechanical wind generator model includes 24 state variables: four mechanical, eleven electrical, and nine more - one for each controller - associated to the control system. The developed model is complemented with a state machine that implements the sequential control among the different stages that define its operational modes. Simulation and experimental results show that the developed model is able to predict the behaviour of the generator in short and long term scenarios. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:428 / 439
页数:12
相关论文
共 37 条
[31]   Grid current regulation of a three-phase voltage source inverter with an LCL input filter [J].
Twining, E ;
Holmes, DG .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2003, 18 (03) :888-895
[32]  
Wu F, 2007, IET GENER TRANSM DIS, V1, P751, DOI 10.1049/ict-gtd:20060395
[33]  
Yongbo Yang, 2009, 2009 IEEE 6th International Power Electronics and Motion Control Conference, P2233, DOI 10.1109/IPEMC.2009.5157774
[34]   A survey of dynamic equivalent modeling for wind farm [J].
Zou, Jianxiao ;
Peng, Chao ;
Yan, Yan ;
Zheng, Hong ;
Li, Yan .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2014, 40 :956-963
[35]   Multi-machine transient modelling of wind farms: An essential approach to the study of fault conditions in the distribution network [J].
Zubia, I. ;
Ostolaza, J. X. ;
Susperregui, A. ;
Ugartemendia, J. J. .
APPLIED ENERGY, 2012, 89 (01) :421-429
[36]   In situ electrical parameter identification method for induction wind generators [J].
Zubia, I. ;
Zatarain, A. ;
Alcalde, C. ;
Ostolaza, X. .
IET ELECTRIC POWER APPLICATIONS, 2011, 5 (07) :549-557
[37]   Complete wind farm electromagnetic transient modelling for grid integration studies [J].
Zubia, I. ;
Ostolaza, X. ;
Susperregui, A. ;
Tapia, G. .
ENERGY CONVERSION AND MANAGEMENT, 2009, 50 (03) :600-610