Performance Evaluation of a CO2 Refrigeration System Enhanced with a Dew Point Cooler

被引:9
作者
Belusko, Martin [1 ]
Liddle, Raymond [1 ]
Alemu, Alemu [1 ]
Halawa, Edward [2 ]
Bruno, Frank [2 ]
机构
[1] Univ South Australia, Barbara Hardy Inst, Sch Engn, Mawson Lakes Campus, Mawson Lakes, SA 5095, Australia
[2] Univ South Australia, Future Ind Inst, Mawson Lakes Campus, Mawson Lakes, SA 5095, Australia
关键词
CO2 refrigeration system; dew point cooler; evaporative cooling; subcritical operation; transcritical operation; EXTREMUM SEEKING CONTROL; MAISOTSENKO CYCLE; HEAT-TRANSFER; CARBON-DIOXIDE; GAS COOLER; AIR; OPTIMIZATION; EFFICIENCIES; FLOW;
D O I
10.3390/en12061079
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Dew point cooling (DPC) is a novel indirect evaporative cooling concept capable of delivering air temperatures approaching the dew point. Coupling this technology with CO2 refrigeration is well suited to minimising transcritical operation when the coefficient of performance (COP) is dramatically reduced in hot climates. A substantial experimental program was conducted to characterise this combination by testing a 20 kW CO2 refrigeration system subject to ambient temperatures above 40 degrees C. It was demonstrated that DPC operation not only avoided transcritical operation during such weather conditions, but also increased the COP by up to 140% compared to the conventional system. The combination of these technologies was successfully mathematically modelled, from which the optimum condenser inlet air temperature was identified for each condenser temperature. Using this optimum condition, it was possible to maximise the COP for a range of conditions applicable to the psychometric chart. An annual case study for Adelaide, Australia was conducted which demonstrated that optimally coupling DPC with CO2 refrigeration can reduce the annual energy consumption and peak demand by 16% and 47%, respectively, compared to a conventional CO2 booster system. Furthermore, the number of hours of transcritical operation was reduced from 3278 to 27.
引用
收藏
页数:22
相关论文
共 29 条
[21]   Efficiencies of transcritical CO2 cycles with and without an expansion turbine [J].
Robinson, DM ;
Groll, EA .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1998, 21 (07) :577-589
[22]  
Rubin A.M., 1975, E1112673 FRANKL I RE
[23]  
Santosa I.D.M.C., 2015, THESIS
[24]   Investigations into air and refrigerant side heat transfer coefficients of finned-tube CO2 gas coolers [J].
Santosa, IDewa M. C. ;
Gowreesunker, Baboo L. ;
Tassou, Savvas A. ;
Tsamos, Konstantinos M. ;
Ge, Yunting .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2017, 107 :168-180
[25]   Optimization of a transcritical CO2 heat pump cycle for simultaneous cooling and heating applications [J].
Sarkar, J ;
Bhattacharyya, S ;
Gopal, MR .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (08) :830-838
[26]  
Sawalha S., 2008, THESIS
[27]   Experimental evaluation of a solid desiccant system integrated with cross flow Maisotsenko cycle evaporative cooler [J].
Shahzad, M. Kashif ;
Chaudhary, Ghulam Qadar ;
Ali, Muzaffar ;
Sheikh, Nadeem Ahmed ;
Khalil, M. Shahid ;
Rashid, Tanzeel Ur .
APPLIED THERMAL ENGINEERING, 2018, 128 :1476-1487
[28]   Comparative analysis of various CO2 configurations in supermarket refrigeration systems [J].
Sharma, Vishaldeep ;
Fricke, Brian ;
Bansal, Pradeep .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2014, 46 :86-99
[29]  
United Nations Environment Programme (UNEP), 2017, RAT KIG AM BRIEF NOT