A demand-oriented approach for integrating earth-to-air heat exchangers into buildings for achieving year-round indoor thermal comfort

被引:32
作者
Yang, Dong [1 ,2 ]
Wei, Haibin [1 ,2 ]
Shi, Rui [1 ,2 ]
Wang, Jilibo [1 ,2 ]
机构
[1] Chongqing Univ, Minist Educ, Key Lab Three Gorges Reservoir Reg Ecoenvironm, Chongqing 400045, Peoples R China
[2] Chongqing Univ, Fac Urban Construct & Environm Engn, Chongqing 400045, Peoples R China
基金
中国博士后科学基金; 中国国家自然科学基金;
关键词
Earth-to-air heat exchanger; Low-energy technology; Thermal environment improvement; Nearly-zero-energy building; Inverse design; COOLING SYSTEM; PERFORMANCE ANALYSIS; ENERGY; TUBE; VENTILATION; DESIGN; SOLAR; EAHE; TEMPERATURE; BUOYANCY;
D O I
10.1016/j.enconman.2018.12.071
中图分类号
O414.1 [热力学];
学科分类号
摘要
Earth-to-air heat exchanger (EAHE) is a promising energy-efficient technology for indoor thermal environment regulation; however, it should adapt to both building and climatic conditions. This paper proposes a new inverse approach to determine the parameters of EAHE integrating into buildings and to achieve a prescribed indoor thermal comfort objective. First, the criterion for achieving year-round thermally comfortable indoor air temperatures is formulated. According to the objective, the required combined parameters characterizing the dynamic behavior of the earth-to-air heat exchanger outlet-air temperature are inversely calculated. Then, the earth-to-air heat exchanger parameters, such as length, radius, burial depth and flow rate, satisfying the proposed objective are determined. The results demonstrate that decreasing the phase shift of the anticipated indoor air temperature profile helps to reduce the requirements on earth-to-air heat exchanger parameters. A Computational Fluid Dynamics simulation incorporated with real meteorological date is implemented according to the EAHE parameters obtained from the proposed approach. It is demonstrated the proposed inverse approach is effective and the year-round indoor thermal comfort is achievable.
引用
收藏
页码:95 / 107
页数:13
相关论文
共 41 条
  • [1] Parametric study on thermal performance of horizontal earth pipe cooling system in summer
    Ahmed, S. F.
    Amanullah, M. T. O.
    Khan, M. M. K.
    Rasul, M. G.
    Hassan, N. M. S.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2016, 114 : 324 - 337
  • [2] The cooling potential of earth-air heat exchangers for domestic buildings in a desert climate
    Al-Ajmi, F
    Loveday, DL
    Hanby, VI
    [J]. BUILDING AND ENVIRONMENT, 2006, 41 (03) : 235 - 244
  • [3] A review on recent size optimization methodologies for standalone solar and wind hybrid renewable energy system
    Al-Falahi, Monaaf D. A.
    Jayasinghe, S. D. G.
    Enshaei, H.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2017, 143 : 252 - 274
  • [4] A model for integrating passive and low energy airflow components into low rise buildings
    Alemu, Alemu T.
    Saman, Wasim
    Belusko, Martin
    [J]. ENERGY AND BUILDINGS, 2012, 49 : 148 - 157
  • [5] Design of a novel geothermal heating and cooling system: Energy and economic analysis
    Angrisani, G.
    Diglio, G.
    Sasso, M.
    Calise, F.
    d'Accadia, M. Dentice
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2016, 108 : 144 - 159
  • [6] [Anonymous], 2012, Design Code for Heating Ventilation and Air Conditioning of Civil Buildings
  • [7] [Anonymous], 2015, 501892015 GB
  • [8] [Anonymous], 2015, 500192015 GB
  • [9] Performance analysis of earth-pipe-air heat exchanger for summer cooling
    Bansal, Vikas
    Misra, Rohit
    Das Agrawal, Ghanshyam
    Mathur, Jyotirmay
    [J]. ENERGY AND BUILDINGS, 2010, 42 (05) : 645 - 648
  • [10] Performance analysis of earth-pipe-air heat exchanger for winter heating
    Bansal, Vikas
    Misra, Rohit
    Das Agrawal, Ghanshyam
    Mathur, Jyotirmay
    [J]. ENERGY AND BUILDINGS, 2009, 41 (11) : 1151 - 1154