Evaluation of a flue gas driven open absorption system for heat and water recovery from fossil fuel boilers

被引:54
|
作者
Wang, Zhenying [1 ]
Zhang, Xiaoyue [2 ]
Li, Zhen [1 ]
机构
[1] Tsinghua Univ, Dept Engn Mech, Minist Educ, Key Lab Thermal Sci & Power Engn, Beijing 100084, Peoples R China
[2] Tsinghua Univ, Beijing Key Lab Heat Transfer & Energy Convers, Beijing 100084, Peoples R China
基金
中国国家自然科学基金;
关键词
Industrial flue gas; Total heat recovery; Open absorption; Regeneration source; Experimental study; FIRED BOILER; PUMP;
D O I
10.1016/j.enconman.2016.09.050
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents an open absorption system for total heat recovery from fossil fuel boilers using the high temperature flue gas as the regeneration heat source, In this system, liquid desiccant serves as the recycling medium, which, absorbs waste heat and moisture contained in the low temperature flue gas in the packed tower and then regenerates in the regenerator by the high temperature flue gas. Water vapor generated in the regenerator gets condensed after releasing heat to the heating water system and the condensing water also gets recycled. The return water collects heat from the solution water heat exchanger, the flue gas water heat exchanger and the condenser respectively and is then used for district heating. Driven by the vapor pressure difference between high humidity flue gas and the liquid desiccant, the heat recovery efficiency of the system is not limited by the dew point of the flue gas, enabling a warmer water to be heated up than the conventional condensing boiler. The performance of this system was analyzed theoretically and experimentally and the results showed that the system operated well for both district heat supply and domestic hot water supply. The system efficiency increased with the moisture content of flue gas and the total heat recovery was about 8.5%, 17.2%, 21.2%, and 9.2% higher than the conventional condensing system in the case of coal fired boiler, fuel oil boiler, natural gas boiler, and coke oven gas boiler, respectively. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:57 / 65
页数:9
相关论文
共 50 条
  • [21] Waste heat recovery from coal-fired boiler flue gas: Performance optimization of a new open absorption heat pump
    Zhang, Hao
    Dong, Yong
    Lai, Yanhua
    Zhang, Xinbo
    APPLIED THERMAL ENGINEERING, 2021, 183
  • [22] Effect of gas nonlinearity on boilers equipped with vapor-pump (BEVP) system for flue-gas heat and moisture recovery
    Wang, Jingyi
    Hua, Jing
    Fu, Lin
    Zhou, Ding
    ENERGY, 2020, 198
  • [23] Experimental Investigation on Solution Regeneration Performance and Coefficients in Full-Open System for Heat and Water Recovery of Flue Gas
    Wei, Hongyang
    Huang, Shifang
    Ma, Yuxin
    Chen, Bo
    Sun, Li
    Zhang, Xiaosong
    JOURNAL OF THERMAL SCIENCE, 2024, 33 (03) : 1094 - 1108
  • [24] Performance analysis of a novel double stage multifunctional open absorption heat pump system: An industrial moist flue gas heat recovery application
    Shahzad, Muhammad Kashif
    Ding, Yaqi
    Xuan, Yongmei
    Gao, Neng
    Chen, Guangming
    ENERGY CONVERSION AND MANAGEMENT, 2022, 254
  • [25] Experimental Investigation on Solution Regeneration Performance and Coefficients in Full-Open System for Heat and Water Recovery of Flue Gas
    WEI Hongyang
    HUANG Shifang
    MA Yuxin
    CHEN Bo
    SUN Li
    ZHANG Xiaosong
    Journal of Thermal Science, 2024, 33 (03) : 1094 - 1108
  • [26] 40% CHEAPER FLUE GAS TREATMENT THROUGH FLEXIBLE HEAT RECOVERY WITH WASTE HEAT BOILERS.
    de Vries, M.
    Sulzer Technical Review, 1987, 69 (02): : 31 - 32
  • [27] Techno-economic study of a heat pump enhanced flue gas heat recovery for biomass boilers
    Hebenstreit, B.
    Schnetzinger, R.
    Ohnmacht, R.
    Hoeftberger, E.
    Lundgren, J.
    Haslinger, W.
    Toffolo, A.
    BIOMASS & BIOENERGY, 2014, 71 : 12 - 22
  • [28] Macroporous ceramic membrane condenser for water and heat recovery from flue gas
    Xiao, Liehui
    Yang, Minlin
    Yuan, Wu-Zhi
    Huang, Si-Min
    APPLIED THERMAL ENGINEERING, 2021, 186
  • [29] APPLICATION OF EVAPORATIVE COOLING FOR THE CONDENSATION OF WATER VAPORS FROM A FLUE GAS WASTE HEAT BOILERS CCP
    Galashov, Nikolay
    Tsibulskiy, Svyatoslav
    Kiselev, Alexander
    HEAT AND MASS TRANSFER IN THE SYSTEM OF THERMAL MODES OF ENERGY - TECHNICAL AND TECHNOLOGICAL EQUIPMENT (HMTTSC-2016), 2016, 72
  • [30] Applicability of self-driven humid and hot flue gas waste heat recovery system
    Zhang C.
    Lin J.
    Cui T.
    Wang Z.
    Li Y.
    Tan Y.
    Harbin Gongye Daxue Xuebao/Journal of Harbin Institute of Technology, 2020, 52 (12): : 164 - 169