Numerical prediction of local hot-spot phenomena in transformer windings

被引:90
作者
Skillen, Alex [1 ]
Revell, Alistair [1 ]
Iacovides, Hector [1 ]
Wu, Wei [2 ]
机构
[1] Univ Manchester, Sch MACE, Modelling & Simulat Ctr, Computat Fluid Dynam Grp, Manchester M13 9PL, Lancs, England
[2] Univ Manchester, Sch EEE, Elect Energy & Power Syst Grp, Manchester M13 9PL, Lancs, England
关键词
Power transformer; CFD modelling; COOLANT FLOW DISTRIBUTION; FUNDAMENTAL APPROACH; PRESSURE LOSS; PART II; PARAMETERS;
D O I
10.1016/j.applthermaleng.2011.11.054
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper, an open source CFD code is used for predicting the mixed-convection flow of coolant in a low-voltage transformer winding. A significant feature of these flows is the high Prandtl number of the dielectric coolant fluid. It is found that for the geometry under consideration, the CFD model predicts the presence of hot-plumes in some of the horizontal cooling ducts. This appears to be due to the highly non-uniform mass flow distribution around the winding, which arises as a result of an inhomogeneous temperature profile across the individual vertical ducts (a direct consequence of high fluid Prandtl number). These hot-plumes are particularly problematic since local heating can cause thermal degradation of the paper insulation. It is also found that there is a strong coupling between the flow in different passes, which is communicated via persistent hot streaks in the fluid being convected from one pass to the next. The importance of these hot streaks is apparent from the CFD results, yet they are unresolved by the lumped parameter based 'network models' preferred by industry, which assume perfect mixing and homogeneous flow quantities in all cooling ducts. In particular, these methods are unable to account for the persistence of these inhomogeneous features from one pass to the next. While it is expected that CFD approaches should provide higher detail than network modelling, the insight gained from the present simulations would suggest that significant changes to current industrial approaches might be necessary in order to correctly account for the observed phenomena. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:96 / 105
页数:10
相关论文
共 14 条
[1]   Numerical study of heat transfer and fluid flow in a power transformer [J].
El Wakil, N ;
Chereches, NC ;
Padet, J .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2006, 45 (06) :615-626
[2]  
Kranenborg E. J., 2008, P 5 EUR THERM SCI C
[3]  
Launder B. E., 1974, Letters in Heat and Mass Transfer, V1, P131, DOI 10.1016/0094-4548(74)90150-7
[4]  
Mechitoua N, 2004, INT J FINITE VOLUMES, V1
[5]  
Oh K.-J., 1999, HEAT TRANSFER ASIAN, V28, P429
[7]   Basics of Detailed Thermal-Hydraulic Model for Thermal Design of Oil Power Transformers [J].
Radakovic, Zoran R. ;
Sorgic, Marko S. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (02) :790-802
[8]  
Ramos J. Gastelurrutiaj., APPL THERMAL ENG
[9]   A simple method for calculating winding temperature gradient in power transformers [J].
Ryder, SA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (04) :977-982
[10]   A fundamental approach to transformer thermal modeling - Part I: Theory and equivalent circuit [J].
Swift, G ;
Molinski, TS ;
Lehn, W .
IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (02) :171-175