Silicone insulators of power transmission lines with a variable inorganic load concentration: Electrical and physiochemical analyses

被引:14
作者
Cardoso, Rodolfo [1 ]
Balestro, Ana Claudia [2 ]
Dellallibera, Adriano [2 ]
Costa, Eduardo Coelho M. [3 ]
Angelini, Joceli Maria G. [4 ]
Innocentini Mei, Lucia Helena [1 ]
机构
[1] Univ Estadual Campinas, Unicamp, Fac Chem Engn, Campinas, SP, Brazil
[2] Ind Eletromecan Balestro Ltda, Mogi Mirim, SP, Brazil
[3] Univ Estadual Paulista, Unesp, Fac Engn Ilha Solteira, Depto Engn Elet, Ilha Solteira, SP, Brazil
[4] Ctr Pesquisa Desenvolvimento Telecomunicacoes CPq, Campinas, SP, Brazil
关键词
Silicone insulators; Electric tracking; Erosion test; Physiochemical measurements; Scanning electronic microscopy; Dispersive spectroscopy X-ray;
D O I
10.1016/j.measurement.2013.12.030
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Polymeric insulation is an increasing tendency in projects and maintenance of electrical networks for power distribution and transmission. Electrical power devices (e. g., insulators and surge arresters) developed by using polymeric insulation presents many advantages compared to the prior power components using ceramic insulation, such as: a better performance under high pollution environment; high hydrophobicity; high resistance to mechanical, electrical and chemical stresses. The practice with silicone insulators in polluted environments has shown that the ideal performance is directly related to insulator design and polymer formulation. One of the most common misunderstandings in the design of silicone compounds for insulators is the amount of inorganic load used in their formulation. This paper attempts to clarify how the variation of the inorganic load amount affects physicochemical characteristics of different silicone compounds. The physicochemical evaluation is performed from several measurements, such as: density, hardness, elongation, tensile strength. In addition, the evaluation of the physicochemical structure is carried out using infrared test and scanning electronic microscopy (SEM). The electrical analysis is performed from the electric tracking wheel and erosion test, in agreement with the recommendation of the International Electrotechnical Commission (IEC). (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:63 / 73
页数:11
相关论文
共 16 条
[1]  
[Anonymous], 1998, 10296 NBR
[2]  
[Anonymous], 2006, D412 ASTM
[3]  
[Anonymous], 2004, D2303 ASTM
[4]  
*ASTM, 2000, D624 ASTM
[5]   Condition assessment of EPDM composite insulators using FTIR spectroscopy [J].
Blackmore, PD ;
Birtwhistle, D ;
Cash, GA ;
George, GA .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1998, 5 (01) :132-141
[6]   Reliability of directly-molded polymer surge arresters: Degradation by immersion test versus electrical performance [J].
da Silva, Daiana Antonio ;
Marques da Costa, Eduardo Coelho ;
De Franco, Jorge Luiz ;
Antonionni, Marcel ;
de Jesus, Rodolfo Cardoso ;
Abreu, Sanderson Rocha ;
Lahti, Kari ;
Innocentini Mei, Lucia Helena ;
Pissolato, Jose .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 53 :488-498
[7]  
ELETROBRAS, 1999, PLAN DEC EXP 1999 20
[8]   REAL-TIME ANALYSIS OF THE THERMAL-OXIDATION OF POLYOLEFINS BY FT-IR EMISSION [J].
GEORGE, GA ;
CELINA, M ;
VASSALLO, AM ;
COLECLARKE, PA .
POLYMER DEGRADATION AND STABILITY, 1995, 48 (02) :199-210
[9]  
Gonzalez E.G.C., 1999, THESIS RIO DE JANEIR
[10]  
*IEC, 1995, 61109 IEC