A novel transient rotor current control scheme of a doubly-fed induction generator equipped with superconducting magnetic energy storage for voltage and frequency support

被引:2
作者
Shen Yang-Wu [1 ]
Ke De-Ping [1 ]
Sun Yuan-Zhang [1 ]
Kirschen, Daniel [2 ]
Wang Yi-Shen [2 ]
Hu Yuan-Chao [1 ]
机构
[1] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Peoples R China
[2] Univ Washington, Dept Elect Engn, Seattle, WA 98195 USA
基金
中国国家自然科学基金;
关键词
doubly-fed induction generator; transient rotor current control; superconducting magnetic energy storage; voltage support; RIDE-THROUGH STRATEGY; DFIG WIND TURBINES;
D O I
10.1088/1674-1056/24/7/070201
中图分类号
O4 [物理学];
学科分类号
0702 ;
摘要
A novel transient rotor current control scheme is proposed in this paper for a doubly-fed induction generator (DFIG) equipped with a superconducting magnetic energy storage (SMES) device to enhance its transient voltage and frequency support capacity during grid faults. The SMES connected to the DC-link capacitor of the DFIG is controlled to regulate the transient dc-link voltage so that the whole capacity of the grid side converter (GSC) is dedicated to injecting reactive power to the grid for the transient voltage support. However, the rotor-side converter (RSC) has different control tasks for different periods of the grid fault. Firstly, for Period I, the RSC injects the demagnetizing current to ensure the controllability of the rotor voltage. Then, since the dc stator flux degenerates rapidly in Period II, the required demagnetizing current is low in Period II and the RSC uses the spare capacity to additionally generate the reactive (priority) and active current so that the transient voltage capability is corroborated and the DFIG also positively responds to the system frequency dynamic at the earliest time. Finally, a small amount of demagnetizing current is provided after the fault clearance. Most of the RSC capacity is used to inject the active current to further support the frequency recovery of the system. Simulations are carried out on a simple power system with a wind farm. Comparisons with other commonly used control methods are performed to validate the proposed control method.
引用
收藏
页数:12
相关论文
共 38 条
[1]   Supercapacitor energy storage for wind energy applications [J].
Abbey, Chad ;
Joos, Geza .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2007, 43 (03) :769-776
[2]   Control of offshore DFIG-based wind farm grid with line-commutated HVDC connection [J].
Bozhko, Serhiy V. ;
Blasco-Gimenez, Ramon ;
Li, Risheng ;
Clare, Jon C. ;
Asher, Greg M. .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2007, 22 (01) :71-78
[3]   Passive adaptive control of chaos in synchronous reluctance motor [J].
Du-Qu, Wei ;
Xiao-Shu, Luo .
CHINESE PHYSICS B, 2008, 17 (01) :92-97
[4]  
Gholizadeh H, 2012, CHINESE PHYS B, V21
[5]   SMES for power utility applications: A review of technical and cost considerations [J].
Karasik, V ;
Dixon, K ;
Weber, C ;
Batchelder, B ;
Campbell, G ;
Ribeiro, P .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 1999, 9 (02) :541-546
[6]   An improved fault ride-through strategy for doubly fed induction generator-based wind turbines [J].
Kasem, A. H. ;
El-Saadany, E. F. ;
El-Tamaly, H. H. ;
Wahab, M. A. A. .
IET RENEWABLE POWER GENERATION, 2008, 2 (04) :201-214
[7]   Impulsive control for permanent magnet synchronous motors with uncertainties: LMI approach [J].
Li Dong ;
Wang Shi-Long ;
Zhang Xiao-Hong ;
Yang Dan .
CHINESE PHYSICS B, 2010, 19 (01)
[8]  
Liu Y S, 2015, P IEEE APPL POW EL C, P697
[9]  
Liu Y S, 2014, P IEEE 5 INT S POW E, P1
[10]  
Liu YS, 2014, IEEE ENER CONV, P964, DOI 10.1109/ECCE.2014.6953503