Optimal Voltage-Support Control for Distributed Generation Inverters in RL Grid-Faulty Networks

被引:35
作者
Garnica, Miguel [1 ,2 ]
de Vicuna, Luis Garcia [2 ]
Miret, Jaume [2 ]
Castilla, Miguel [2 ]
Guzman, Ramon [3 ]
机构
[1] Escuela Naval Cadetes Almirante Padilla, Grp Invest Comunicac Control & Diseno Naval, Cartagena 130001, Colombia
[2] Tech Univ Catalonia, Dept Elect Engn, Barcelona 08800, Spain
[3] Tech Univ Catalonia, Dept Automat Control, Barcelona 08800, Spain
关键词
Inverters; Impedance; Voltage control; Power quality; Oscillators; Reactive power; Power system stability; Active power control; active power oscillation cancellation; distributed power generation; maximum current injection; reactive power control; unbalanced grid faults; voltage ride-through; voltage sag; voltage support; REFERENCE LIMITATION METHOD; SHUNT-CONNECTED CONVERTERS; AVOID EXCEEDING VOLTAGE; CONTROL STRATEGIES; 3-PHASE INVERTERS; CURRENT LIMITS; CONTROL SCHEME; MAXIMIZE; CAPABILITY; PLANTS;
D O I
10.1109/TIE.2019.2949544
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
During grid faults, the stability and reliability of the network are compromised, and the risk of a widespread disconnection of distributed generation power facilities is increased. Distributed generation inverters must support the power system to prevent this issue. Voltage support depends substantially on the currents injected into the grid and the equivalent grid impedance. This article considers these two aspects and proposes an optimal voltage-support strategy in RL grids. The control algorithm guarantees safe operation of the inverter during voltage sags by calculating the appropriate reference currents according to the equivalent impedance and the voltage sag characteristics, avoiding active power oscillations, and limiting the injected current to the maximum allowed by the inverter. Consequently, the grid can be better supported since the voltage at the point of common coupling is improved and the voltage support objectives are achieved. The proposed control strategy is validated through experimental tests in different grid scenarios. Throughout this article, it is assumed that the grid impedance is known, but the proposed solution requires calculating the grid impedance angle.
引用
收藏
页码:8405 / 8415
页数:11
相关论文
共 41 条
[1]   Control Strategies Based on Symmetrical Components for Grid-Connected Converters Under Voltage Dips [J].
Alepuz, Salvador ;
Busquets-Monge, Sergio ;
Bordonau, Josep ;
Martinez-Velasco, Juan A. ;
Silva, Cesar A. ;
Pontt, Jorge ;
Rodriguez, Jose .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2009, 56 (06) :2162-2173
[2]   Overview of Recent Grid Codes for Wind Power Integration [J].
Altin, Muefit ;
Goeksu, Oemer ;
Teodorescu, Remus ;
Rodriguez, Pedro ;
Jensen, Birgitte-Bak ;
Helle, Lars .
OPTIM 2010: PROCEEDINGS OF THE 12TH INTERNATIONAL CONFERENCE ON OPTIMIZATION OF ELECTRICAL AND ELECTRONIC EQUIPMENT, PTS I-IV, 2010, :1152-+
[3]  
[Anonymous], 2016, DISTR COD APPR CER
[4]  
[Anonymous], 1994, 141TM1993 IEEE
[5]  
[Anonymous], 1999, TR112692 EPRI
[6]  
[Anonymous], 2013, NETW COD REQ GRID CO
[7]  
[Anonymous], 2006, P 12 3 RESP REQ VOLT
[8]   Implementation and test of an online embedded grid impedance estimation technique for PV inverters [J].
Asiminoaei, L ;
Teodorescu, R ;
Blaabjerg, F ;
Borup, U .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2005, 52 (04) :1136-1144
[9]   Overview of control and grid synchronization for distributed power generation systems [J].
Blaabjerg, Frede ;
Teodorescu, Remus ;
Liserre, Marco ;
Timbus, Adrian V. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2006, 53 (05) :1398-1409
[10]  
Blackburn JL, 2006, PROTECTIVE RELAYING, V3rd