Instrumented Static Load Test on Rock-Socketed Micropile

被引:33
|
作者
Seo, Hoyoung [1 ]
Prezzi, Monica [2 ]
Salgado, Rodrigo [2 ]
机构
[1] Texas Tech Univ, Dept Civil & Environm Engn, Lubbock, TX 79409 USA
[2] Purdue Univ, Sch Civil Engn, W Lafayette, IN 47907 USA
关键词
Micropiles; Pile load tests; Load-bearing capacity; Rocks; DRILLED PIERS; SHAFT LENGTH; CAPACITY; RESISTANCE; DRIVEN; DESIGN; PILES;
D O I
10.1061/(ASCE)GT.1943-5606.0000946
中图分类号
P5 [地质学];
学科分类号
0709 ; 081803 ;
摘要
Rock-socketed piles are often used to transfer heavy loads from a superstructure to competent underlying rock layers. The loads are transferred by the pile to the surrounding rock mass through shaft and base resistance. Several researchers have investigated the behavior of rock-socketed drilled shafts and related the uniaxial compressive strength of intact rock to pile-shaft resistance. However, the load-transfer behavior and load-settlement response of micropiles are different from those of drilled shafts because of the large slenderness ratio (pilelength/pilediameter) of micropiles. This study presents results from a fully instrumented field-scale load test on a 0.2-m-diameter micropile socketed 4.2 m into limestone layers (2.7 m into weathered limestone and 1.5 m into hard limestone). The results show that practically no base resistance is mobilized until the pile-head settlement reaches approximately 7% of the diameter of the test micropile. The measured limit shaft resistance values are compared with values predicted using methods available in the literature. The comparison indicates that use of the intact strength of the rock for estimation of limit shaft resistance may lead to an unconservative design when the rock mass quality is very poor, as indicated by, for example, low rock-quality designation values.
引用
收藏
页码:2037 / 2047
页数:11
相关论文
empty
未找到相关数据