Experimental investigation of the temperatures and performance of a commercial ice-storage tank

被引:30
作者
Lopez-Navarro, A. [1 ]
Biosca-Taronger, J. [1 ]
Torregrosa-Jaime, B. [1 ]
Martinez-Galvan, I. [1 ]
Corberan, J. M. [1 ]
Esteban-Matias, J. C. [2 ]
Paya, J. [1 ]
机构
[1] Univ Politecn Valencia, IIE, Valencia 46022, Spain
[2] ACCIONA Infraestruct SA, Ctr Innovac Tecnol, Madrid 28108, Spain
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2013年 / 36卷 / 04期
关键词
Thermal storage; Experimental installation; Ice formation; Energy consumption; THERMAL-ENERGY STORAGE; SLURRY APPLICATIONS; HORIZONTAL TUBE; PHASE-CHANGE; WATER; PROBABILITY; NUCLEATION; SYSTEMS;
D O I
10.1016/j.ijrefrig.2012.09.008
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents the results of an experimental installation with an internal melt-ice-on-coil tank which has a total capacity of 172 kWh. The aim of this work is to analyse the freezing process in a tank with counter-current spiral-shaped coils immersed in around 1855l water. An experimental campaign has been performed with different inlet temperatures and mass flow rates of the heat transfer fluid. This study analyses (i) the chiller performance, (ii) the ice-formation process and (iii) the energy consumption of the installation. Supply temperatures between -2.5 degrees C and -5.2 degrees C have been sufficient to charge the tank without using any nucleating agents. The lowest energy consumption has been achieved for the fastest charging tests. (C) 2012 Elsevier Ltd and IIR. All rights reserved.