Thermal characteristics and their relevance to spontaneous ignition of refuse plastics/paper fuel

被引:19
作者
Li, Xin-Rui [1 ]
Lim, Woo-Sub [1 ]
Iwata, Yusaku [1 ]
Koseki, Hiroshi [1 ]
机构
[1] Natl Res Inst Fire & Disaster, Chofu, Tokyo 1828508, Japan
关键词
Refuse paper and plastic fuel (RPF); Thermal property; Calorimetry; Self-heating; Spontaneous ignition;
D O I
10.1016/j.jlp.2008.09.004
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
Being used as a new type of solid fuel, refuse plastics/paper fuel (RPF) is made up of waste paper and a variety of plastics such as polyethylene, polypropylene, polystyrene, polyvinyl chloride, etc. It is imperative to examine the thermal and self-heating behaviors of RPF because of the propensity of spontaneous ignition during its storage. RPF used in this study was sampled from a fire site. A thermogravimetry/differential thermal analysis (TG-DTA) test was carried out to screen its thermal behavior. In comparison, more precise measurements for RPF were conducted in Calvet calorimeters (C 80 and MS 80), in which heating rates were 0.1 and 0.02 degrees C/min, respectively. Isothermal measurement was performed in a thermal activity monitor (TAM) to examine the reaction at 50 degrees C. Spontaneous ignition tests were performed in a wire mesh cube at certain constant environmental temperatures and a spontaneous ignition tester (SIT) under an adiabatic condition. Results showed that measurement conditions, such as heating rate, sample size, sensitivity of calorimetry, and adiabatic condition in storage significantly affect the thermal behaviors of RPF The TG-DTA curves showed that the visible weight loss and exothermic reaction of RPF occurred at a temperature above 170 degrees C. This is caused by the oxidation and degradation of the components in the RPF. Ignition of RPF by self-heating was found at the corresponding temperature in the wire mesh cube. Whereas in C 80 several endothermic peaks, coming from the melting of plastics, were observed in the range of 120-170 degrees C ahead of major exothermic peaks. In MS 80, the thermal properties related to different phases of physical and chemical changes were seen more distinctly in which the start of exothermic process shifted to lower temperature of about 134 degrees C. The relevant spontaneous ignition was confirmed at 118 degrees C by the SIT test. Kinetics of the reaction was analyzed from the above data and the correlation of the critical temperature and the size of pile-up were predicted based on the Frank-Kamenetskii thermal explosion theory. It showed that the spontaneous ignition may start at a lower temperature than the normal expected temperature of 170 degrees C. The reaction at the lower temperature is usually suppressed by the endothermic effect of the melting of plastics; on the other hand, if the heat conductivity condition becomes worse in the RPF storage, the initial exothermic reaction can potentially support self-heating of the volume to the final occurrence of the ignition. (c) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1 / 6
页数:6
相关论文
共 11 条
[1]  
BOWES PC, 1971, 867 FIR RES
[2]  
DRYSDALE D, 1999, INTRO FIRE DYNAMICS, P163
[3]  
FRANKKAMENETSKI.DA, 1969, DIFFUSION HEAT TRANS
[4]   Heat generation of Refuse Derived Fuel with water [J].
Fu, ZM ;
Li, XR ;
Koseki, H .
JOURNAL OF LOSS PREVENTION IN THE PROCESS INDUSTRIES, 2005, 18 (01) :27-33
[5]   Calculation of the Frank-Kamenetskii critical parameter for a cubic reactant shape from experimental results on bituminous coals [J].
Jones, JC .
FUEL, 1999, 78 (01) :89-91
[6]  
KOMAMIYA K, 2004, SAF DIG, V50, P30
[7]   Evaluation of danger from fermentation-induced spontaneous ignition of wood chips [J].
Li, Xin-Rui ;
Koseki, Hiroshi ;
Momota, Michihiko .
JOURNAL OF HAZARDOUS MATERIALS, 2006, 135 (1-3) :15-20
[8]  
OKUBO T, 2005, P 9 KOR JAP JOINT IN, P195
[9]  
The United Nations, 2003, UN GEN ASS 58 210 AC, V4th
[10]  
Vasile C., 2006, J Mater Cycles Waste Manag, V8, P99, DOI DOI 10.1007/S10163-006-0151-Z