An approach to determine the health index of power transformers

被引:82
作者
Naderian, A. [1 ]
Cress, S. [1 ]
Piercy, R. [1 ]
Wang, F. [1 ]
Service, J. [1 ]
机构
[1] Kinectr Inc, Transmiss & Distribut Technol, Toronto, ON M8Z 6C4, Canada
来源
CONFERENCE RECORD OF THE 2008 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2 | 2008年
关键词
D O I
10.1109/ELINSL.2008.4570308
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper describes a realistic Health Index formulation method for power transformers using readily available data. The method considers practical limitations on obtaining data, and the possible constraints on the parameters. It also utilizes EEC, IEEE, and CIGRE criteria for condition parameters. This Health Index calculation considers not only typical test results such as dissolved gas analysis (DGA), oil quality, furan, and power factor, but also other parameters such as tap changer and bushing condition, physical observations, load history, maintenance work orders, and age. The calculation includes condition ratings, weighting factors, and assigned scores for specific condition parameters. By using a multi-criteria analysis approach, the method combines the various factors into a condition-based Health Index.
引用
收藏
页码:192 / 196
页数:5
相关论文
共 14 条
  • [11] *IEEE, 1991, C571041991 IEEE TRAN
  • [12] JAKOB F, 2003, EL MAN COIL WIND C I
  • [13] *W EL COORD COUNC, 2006, SUBST WORKGR M VANC
  • [14] WANG M, 2002, IEEE ELECT INSUL NOV, V18