Analysis and Verification of Strength of 110kV Porcelain Post Insulator

被引:0
|
作者
Jin, Songan [1 ]
Mo, Wenxiong [2 ]
Wei, Jingrong [1 ]
Lu, Guojun [2 ]
Li, Xiyu [1 ]
Wang, Yong [2 ]
Liu, Chaofeng [1 ]
Min, Chao [1 ]
Dang, Zhenping [1 ]
Wang, Le [1 ]
机构
[1] Xian High Voltage Apparat Res Inst Co Ltd, Xian, Shaanxi, Peoples R China
[2] Guangzhou Power Supply Co Ltd, Guangzhou, Guangdong, Peoples R China
关键词
Porcelain post insulator; strength; cantilever beam; porcelain brushing; stress between the sheds;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Porcelain post insulators are widely used in power equipment as insulation-supporting structure. The current standard has clear requirement for the overall strength of porcelain post insulators; however, the operation and maintenance data of various operating conditions show that shed damage is a major failure type of porcelain post insulators. At present, strength verification of cantilever beam is employed in the strength design of porcelain post insulator, focusing on the stress on the root of porcelain, with the strength of the shed and the stress between the sheds not taken into account. In this paper, calculation based on the main type of operation failure of 110kV porcelain post insulators shows that the stress between sheds near the root of porcelain brushing is much larger than that on the root of porcelain brushing, which is proved by experimental verification. According to the result, a good explanation of the phenomenon that a large number of porcelain post insulators damage concentrated in the between the sheds of the root of the porcelain brushing is proposed with the optimization of the current design and test criteria of porcelain post insulator.
引用
收藏
页码:1010 / 1014
页数:5
相关论文
共 50 条
  • [1] Influence of Deteriorated Porcelain Insulator on Electric Field and Potential Distribution of Insulators Strings in 110kV Transmission Lines
    Xu Changfu
    Hu Chengbo
    Xu Jiayuan
    Liu Yunpeng
    Zhang Kaiyuan
    Pei Shaotong
    2017 IEEE INTERNATIONAL CONFERENCE ON SMART GRID AND SMART CITIES (ICSGSC), 2017, : 162 - 166
  • [2] Mechanical strength for winding of 110kV transformer
    Zhou, Qingquan
    Zhuzao Jishu/Foundry Technology, (01): : 1 - 5
  • [3] Development of post porcelain insulator for 1000 kV UHV AC
    Zhang, Qin
    Wang, Shao-Wu
    Wu, Guang-Ya
    Ye, Li-Mao
    Zhang, Rui
    Gaodianya Jishu/High Voltage Engineering, 2010, 36 (06): : 1437 - 1441
  • [4] 110KV optical fiber voltage transformer using a porcelain capacitor divider
    Ye, MY
    Ou, CL
    Cui, Y
    Zhou, JY
    Li, KC
    Chen, ZP
    Xu, Y
    Luo, SA
    OPTICAL AND FIBER OPTIC SENSOR SYSTEMS, 1998, 3555 : 63 - 66
  • [5] Study on the flashover characteristics of bird droppings along 110kV composite insulator
    Wang, Huaqian
    Wang, Shenghui
    Deng, Changyu
    Yang, Guanghua
    Lv, Fangcheng
    2018 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2018, : 2929 - 2933
  • [6] Study on the damage analysis of 110kV cable structure
    He, Zhitao
    He, Wen
    He, Haohui
    Hong, Junxuan
    5TH INTERNATIONAL CONFERENCE ON POWER, ENERGY AND MECHANICAL ENGINEERING (ICPEME 2021), 2021, 243
  • [7] Intelligent prediction of 110kV insulator lightning flashover criteria based on random forest
    He, Shaomin
    Han, Yongxia
    Zhao, Zicai
    Liu, Gang
    Qu, Lu
    Huang, Zhidu
    Zhang, Yaqi
    Liu, Boxuan
    Wu, Zhongyang
    Li, Licheng
    ELECTRIC POWER SYSTEMS RESEARCH, 2024, 232
  • [8] 110kV变电所110kV备自投装置拒动分析
    陈涛
    李明
    科技信息, 2012, (19) : 419 - 419
  • [9] 110kV内桥接线变电站110kV母线故障分析
    王京锋
    陈磊
    沿海企业与科技, 2016, (05) : 52 - 53+51
  • [10] 110kV变电站110kV备自投装置拒动分析
    庄雷明
    孔海波
    陈涛
    周超
    胡耀聪
    李强
    科技视界, 2013, (30) : 289 - 290