A novel modified robust load frequency controller scheme

被引:7
作者
Abo-Elyousr, Farag K. [1 ]
Sharaf, Adel M. [2 ,3 ]
机构
[1] Assiut Univ, Elect Engn Dept, Fac Engn, Assiut 71516, Egypt
[2] Sharaf Energy Syst Inc, Fredericton, NB, Canada
[3] Intelligent Environm Energy Syst Canada Inc, Fredericton, NB, Canada
来源
ENERGY SYSTEMS-OPTIMIZATION MODELING SIMULATION AND ECONOMIC ASPECTS | 2020年 / 11卷 / 04期
关键词
Load frequency control (LFC); Fractional order PI controller; Optimal control; Artificial bee colony (ABC); Virtual inertia generator; Robustness improvements; AUTOMATIC-GENERATION CONTROL; ENERGY-STORAGE; POWER-SYSTEM; ALGORITHM; DESIGN; WIND; OPTIMIZATION; TURBINE; AREA; PV;
D O I
10.1007/s12667-019-00341-3
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The main target of this study is to allow virtual inertia modern distributed energy resources (DERs) to participate effectively within interconnected power systems via fractional order PI controller. Fractional order proportional plus integral (PI) is a PI whose integral order is a faction rather than integer numbers. The load frequency control (LFC) approach determines the fractional order PI parameters based on an artificial bee colony optimization algorithm. Besides, a per phase linearized model for massless DERs was developed for solving LFC issues. In order to avoid the complexity associated with the power systems, the optimization problem was formulated based on a time domain objective function, which is based on the norm of each area control error vector. The time domain simulated evaluations are compared with the classical PI and integral controllers. Simulated results show that the developed factional order PI outperforms the other controllers in terms of damping the oscillations and many system indices.
引用
收藏
页码:1175 / 1198
页数:24
相关论文
共 46 条
[31]  
Panda T. R., 2018, INT J PAVE RES TECH, V1, P1
[32]   A literature survey on load-frequency control for conventional and distribution generation power systems [J].
Pandey, Shashi Kant ;
Mohanty, Soumya R. ;
Kishor, Nand .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 25 :318-334
[33]   Adaptive deloading of stand-alone wind farm for primary frequency control [J].
Pradhan C. ;
Bhende C.N. .
Energy Systems, 2015, 6 (1) :109-127
[34]   Simulation based neuro-fuzzy hybrid intelligent PI control approach in four-area load frequency control of interconnected power system [J].
Prakesh, Surya ;
Sinha, S. K. .
APPLIED SOFT COMPUTING, 2014, 23 :152-164
[35]  
Ramesh S., 2009, International Journal of Electrical Power Engineering, V3, P26
[36]  
RAMEZANIAN H, 2013, INT J CONTROL AUTOM, V6, P55
[37]  
Ranganayakulu R., 2016, Resour.-Effic. Technol, V2, pS136, DOI [10.1016/j.reffit.2016.11.009, DOI 10.1016/J.REFFIT.2016.11.009]
[38]  
SHARAF AM, 2018, CLASSICAL RECENT ASP, P33
[39]   Feasibility study of an islanded microgrid in rural area consisting of PV, wind, biomass and battery energy storage system [J].
Singh, Shakti ;
Singh, Mukesh ;
Kaushik, Subhash Chandra .
ENERGY CONVERSION AND MANAGEMENT, 2016, 128 :178-190
[40]   Sliding mode based load-frequency control in power systems [J].
Vrdoljak, K. ;
Peric, N. ;
Petrovic, I. .