An Innovative Pilot Relaying Scheme for Shunt-Compensated Line

被引:32
|
作者
Gupta, Om Hari [1 ]
Tripathy, Manoj [1 ]
机构
[1] Indian Inst Technol Roorkee, Dept Elect Engn, Roorkee 247667, Uttarakhand, India
关键词
Fault classification; integrated impedance; pilot relaying; protection of compensated line; static var compensator (SVC); TRANSMISSION-LINES; INTEGRATED IMPEDANCE; DISTANCE PROTECTION; PERFORMANCE; SVC;
D O I
10.1109/TPWRD.2015.2394353
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a fault detection and classification scheme for a shunt [static var compensator (SVC)] compensated line. The proposed relaying scheme is based on the concept of superimposed sequence components-based integrated impedance (SSCII). For an internal fault, the magnitude of SSCII is small and for an external fault, it is very large. In the SVC compensated line, a fault forces SVC to vary its impedance. Superimposed components are injected due to this impedance variation, along with the fault components. These SVC-injected components are treated as fault-injected components and, therefore, even the sound phases are detected as faulty phases. To avoid such failure, fault-injected superimposed components have been extracted by using the modified prefault data, which is estimated according to SVC impedance variations. The superimposed components measured using the modified prefault data consist of fault-injected superimposed components only. The proposed scheme has been tested for all types of faults, different values of fault resistances, and several fault locations and SVC locations. The results demonstrate that the proposed scheme successfully detects and classifies the faults. Also, the proposed scheme is robust against variations in fault resistance, source impedance, and SVC location.
引用
收藏
页码:1439 / 1448
页数:10
相关论文
共 50 条
  • [41] An Innovative Directional Relaying Scheme Based on Postfault Current
    Jalilian, A.
    Hagh, M. Tarafdar
    Hashemi, S. M.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (06) : 2640 - 2647
  • [42] Damaging Open-Phase Overvoltage Disturbance on a Shunt-Compensated 500-kV Line Initiated by Unintended Trip (vol 30, pg 412, 2015)
    Nagpal, M.
    Martinich, T. G.
    Bimbhra, A.
    Sydor, D.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (02) : 1024 - 1025
  • [43] Directional Relaying of Series-compensated Line Using an Integrated Approach
    Biswal, M.
    Pati, B. B.
    Pradhan, A. K.
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2012, 40 (07) : 691 - 710
  • [44] Pattern recognition based digital relaying for advanced series compensated line
    Samantaray, S. R.
    Dash, P. K.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2008, 30 (02) : 102 - 112
  • [45] Differential energy based relaying for thyristor controlled series compensated line
    Samantaray, S. R.
    Tripathy, L. N.
    Dash, P. K.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2012, 43 (01) : 621 - 629
  • [46] A Dual-Time Transform Assisted Intelligent Relaying Scheme for the STATCOM-Compensated Transmission Line Connecting Wind Farm
    Biswas, Sauvik
    Nayak, Paresh
    Pradhan, Gayadhar
    IEEE SYSTEMS JOURNAL, 2022, 16 (02): : 2160 - 2171
  • [47] Adaptive Distance Relay Algorithm for Shunt Compensated Transmission Line
    Biswal, Sandeep
    Biswal, Monalisa
    2016 INTERNATIONAL CONFERENCE ON ELECTRICAL POWER AND ENERGY SYSTEMS (ICEPES), 2016, : 426 - 431
  • [48] A New Digital Relaying Scheme for Parallel Transmission Line
    Bhalja, Bhavesh
    Maheshwari, Rudra Prakash
    Parikh, Urmil B.
    INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS, 2009, 10 (03):
  • [49] A new digital relaying scheme for parallel transmission line
    ADIT, 388121, India
    不详
    不详
    Int. J. Emerg. Electr. Power Syst., 2009, 3
  • [50] A Positive-Sequence Directional Relaying Algorithm for Series-Compensated Line
    Jena, Premalata
    Pradhan, Ashok Kumar
    IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) : 2288 - 2298