An Innovative Pilot Relaying Scheme for Shunt-Compensated Line

被引:32
作者
Gupta, Om Hari [1 ]
Tripathy, Manoj [1 ]
机构
[1] Indian Inst Technol Roorkee, Dept Elect Engn, Roorkee 247667, Uttarakhand, India
关键词
Fault classification; integrated impedance; pilot relaying; protection of compensated line; static var compensator (SVC); TRANSMISSION-LINES; INTEGRATED IMPEDANCE; DISTANCE PROTECTION; PERFORMANCE; SVC;
D O I
10.1109/TPWRD.2015.2394353
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a fault detection and classification scheme for a shunt [static var compensator (SVC)] compensated line. The proposed relaying scheme is based on the concept of superimposed sequence components-based integrated impedance (SSCII). For an internal fault, the magnitude of SSCII is small and for an external fault, it is very large. In the SVC compensated line, a fault forces SVC to vary its impedance. Superimposed components are injected due to this impedance variation, along with the fault components. These SVC-injected components are treated as fault-injected components and, therefore, even the sound phases are detected as faulty phases. To avoid such failure, fault-injected superimposed components have been extracted by using the modified prefault data, which is estimated according to SVC impedance variations. The superimposed components measured using the modified prefault data consist of fault-injected superimposed components only. The proposed scheme has been tested for all types of faults, different values of fault resistances, and several fault locations and SVC locations. The results demonstrate that the proposed scheme successfully detects and classifies the faults. Also, the proposed scheme is robust against variations in fault resistance, source impedance, and SVC location.
引用
收藏
页码:1439 / 1448
页数:10
相关论文
共 13 条
[1]   Performance comparison of distance protection schemes for Shunt-FACTS compensated transmission lines [J].
Albasri, Fadhel A. ;
Sidhu, Tarlochan Singh ;
Varma, Rajiv K. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (04) :2116-2125
[2]  
[Anonymous], 2013, PSCAD EMTDC 4 5 2 0
[3]   Operation of impedance protection relays with the STATCOM [J].
El-Arroudi, K ;
Joos, G ;
McGillis, DT .
IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (02) :381-387
[4]   Accurate fault location algorithm for transmission lines in the presence of shunt-connected flexible AC transmission system devices [J].
Ghazizadeh-Ahsaee, M. ;
Sadeh, J. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2012, 6 (03) :247-255
[5]   Impact of SVC on the protection of transmission lines [J].
Ghorbani, Amir ;
Khederzadeh, Mojtaba ;
Mozafari, Babak .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2012, 42 (01) :702-709
[6]   Integrated Impedance-Based Pilot Protection Scheme for the TCSC-Compensated EHV/UHV Transmission Lines [J].
He, Shien ;
Suonan, Jiale ;
Bo, Z. Q. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (02) :835-844
[7]  
Hecht E., 2002, Optics
[8]  
Hingorani Narain., 2000, Understanding FACTS: Concepts and Technology of Flexible AC Transmission Systems, P1, DOI DOI 10.1109/9780470546802.CH1
[9]   Directional Relaying in the Presence of a Thyristor-Controlled Series Capacitor [J].
Jena, Premalata ;
Pradhan, Ashok Kumar .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (02) :628-636
[10]  
Padiyar K. R., 2007, FACTS CONTROLLERS PO, P1