Time Resolved Measurements of X-ray Induced Partial Discharges

被引:0
|
作者
Adili, Sedat [1 ]
Herrmann, Lorenz G. [2 ]
Franck, Christian M. [1 ]
机构
[1] Swiss Fed Inst Technol, Power Syst & High Voltage Labs, CH-8092 Zurich, Switzerland
[2] ABB Switzerland Ltd, Corp Res, CH-5405 Baden, Switzerland
关键词
PD;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The initial statistical time lag of partial discharge (PD) measurements was eliminated by using short x-ray pulses (duration 50 ns) for triggering. Phase resolved PD (PRPD) patterns at low electric field levels were recorded. No significant difference between the PRPD patterns after x-ray pulse triggering and naturally incepted PDs was observed. These measurements were performed with self-produced spherical void samples and even voids of 0.5 mm were detected after one x-ray pulse application. It is assumed that the x-ray pulses provide necessary start electrons to start an avalanche. However, in order to study the effect of the x-ray pulse on the triggering and on the discharge mechanism, time resolved PD measurements with an ultra-wideband detection circuit are necessary. In this work, the classical wide-band PD detection circuit was modified and time resolved measurements were performed. Particular emphasis is placed on the effect of the x-ray dose on the first PD pulses, here shown for one void size. Moreover, the temporal development of subsequent discharges after the total decay of the x-ray pulse is studied. To increase the accuracy of the detection, optical measurements of the discharge are synchronously made with a photomultiplier tube.
引用
收藏
页码:125 / 128
页数:4
相关论文
共 50 条
  • [1] Investigating the Inception Mechanism of Pulsed X-ray Triggered Partial Discharges by Time Resolved Measurements
    Adili, Sedat
    Herrmann, Lorenz G.
    Franck, Christian M.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (05) : 1780 - 1788
  • [2] Pulsed X-ray Induced Partial Discharge: Phase and Time-Resolved Measurements
    Adili, Sedat
    Franck, Christian M.
    Sere, Suna Bolat
    Heiiinann, Lorenz G.
    2011 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS 1 AND 2, 2011, : 32 - 35
  • [3] IMAGING PLATE FOR TIME-RESOLVED X-RAY MEASUREMENTS
    AMEMIYA, Y
    KISHIMOTO, S
    MATSUSHITA, T
    SATOW, Y
    ANDO, M
    REVIEW OF SCIENTIFIC INSTRUMENTS, 1989, 60 (07): : 1552 - 1556
  • [4] Sub-picosecond, time resolved x-ray measurements
    Shepherd, R
    Booth, R
    Young, B
    Price, D
    More, R
    Lee, R
    Stewart, R
    APPLICATIONS OF X RAYS GENERATED FROM LASERS AND OTHER BRIGHT SOURCES, 1997, 3157 : 2 - 9
  • [5] Ultrafast X-ray sources for time-resolved measurements
    Hada, Masaki
    Matsuo, Jiro
    X-RAY SPECTROMETRY, 2012, 41 (04) : 188 - 194
  • [6] Continuous and pulsed X-ray induced partial discharges: similarities and differences
    Silva, G. C.
    Swinka-Filho, V.
    Robert, R.
    2006 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, 2006, : 598 - 601
  • [7] CORRELATED ELECTRICAL AND X-RAY MEASUREMENTS IN FLASH X-RAY DISCHARGES
    HANDEL, SK
    BERG, JM
    ARKIV FOR FYSIK, 1966, 31 (01): : 1 - +
  • [8] TIME RESOLVED, SUB-KEV, X-RAY MEASUREMENTS USING FILTERED, X-RAY DIODES
    TIRSELL, KG
    KORNBLUM, HN
    SLIVINSKY, VW
    BULLETIN OF THE AMERICAN PHYSICAL SOCIETY, 1978, 23 (07): : 807 - 807
  • [9] Conical x-ray crystal spectrometer for time integrated and time resolved measurements
    Andiel, U
    Eidmann, K
    Pisani, F
    Witte, K
    Uschmann, I
    Wehrhan, O
    Förster, E
    REVIEW OF SCIENTIFIC INSTRUMENTS, 2003, 74 (04): : 2369 - 2374
  • [10] Time-resolved X-ray spectroscopy for X-ray-induced phenomena
    Picon, Antonio
    X-RAY LASERS AND COHERENT X-RAY SOURCES: DEVELOPMENT AND APPLICATIONS, 2017, 10243