Experimental and numerical study of smoke behavior in high-rise stairwells with open and closed windows

被引:14
|
作者
Ahn, Chan-Sol [1 ,2 ]
Kim, Doo-Young [2 ]
Park, Chanwoo [1 ]
Kim, Min-Woo [1 ]
Kim, Taegun [1 ]
Bang, Boo-Hyoung [3 ]
An, Seongpil [4 ,5 ]
Yarin, Alexander L. [6 ]
Yoon, Sam S. [1 ]
机构
[1] Korea Univ, Sch Mech Engn, Seoul 02841, South Korea
[2] Korea Inst Civil Engn & Bldg Technol, Fire Res Ctr, 283 Goyang Daero, Goyang Si 10223, South Korea
[3] Gyeonggi Univ Sci & Technol, Dept Energy Mech Engn, 269 Gyeonggigwagidae Ro, Siheung Si 15073, South Korea
[4] Sungkyunkwan Univ SKKU, SKKU Adv Inst Nanotechnol SAINT, Suwon 16419, South Korea
[5] Sungkyunkwan Univ SKKU, Dept Nano Engn, Suwon 16419, South Korea
[6] Univ Illinois, Dept Mech & Ind Engn, 842 W Taylor St, Chicago, IL 60607 USA
基金
新加坡国家研究基金会;
关键词
Smoke dynamics; High-rise stairwells; Turbulent plume; Flow visualization; Ventilation; Open-windows; LARGE-EDDY SIMULATION; BUOYANT PLUME; TEMPERATURE DISTRIBUTION; HOT GASES; FIRE; VENTILATION; MODEL; DYNAMICS; SHAFTS; FLOW;
D O I
10.1016/j.ijthermalsci.2020.106500
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study numerically and experimentally investigates the transport phenomena in buoyancy-driven smoke inside stairwells in a high-rise building. Hot smoke is supplied at the bottom of a small-scale, 2 m high stairwell prototype, and the smoke velocity and temperature are measured and compared with the corresponding numerical results. For all-windows-closed cases, the Fire Dynamics Simulator (FDS) model is used to predict the smoke velocity and temperature fields, which are found to be in good agreement with the experimental data. Obstruction caused by the stairs is observed to slow the smoke flow, which results in staggering and repeated vortical flows in all stairwells, confirmed by flow visualization. The flow path lines and vortex formation of the smoke inside the stairwells are visualized using the laser-induced fluorescence (LIF) method; these vortical structures also corresponded to the results of FDS simulation. Furthermore, the effect of heating power (Q) is investigated in the range of 60-180 W for experiments and 1-4 kW for simulations. Both temperature and velocity increase with Q. Having one open window at various building heights is shown to have small effect on the overall smoke temperature, although having many open windows causes a temperature drop owing to the inflow of fresh, cool air. Having one open window at various building heights slightly slows the smoke velocity, although the velocity is significantly decreased when many windows are open. Therefore, the intake of fresh air slows the overall smoke dynamics. Moreover, the effect of Q in the range of 2-20 MW over building heights of 60, 120, and 240 m is numerically simulated. The rate at which the smoke reaches high elevations is determined for all-windows-closed and all-windows-open cases based on our parametric studies. The smoke rise time (t) is shown to be proportional to similar to Q(-1/3) for all building heights, which is the same time scale as the one predicted by the plume theory. However, because of the complex internal geometry of confined buildings including stairwells and corridors, the magnitude of the smoke rise time for the building is much larger than that predicted by the plume theory. Therefore, the current experimental and numerical findings may be useful as design guidelines for building safety engineers.
引用
收藏
页数:20
相关论文
共 50 条
  • [1] Theoretical, numerical, and experimental investigation of smoke dynamics in high-rise buildings
    Ahn, Chan-Sol
    Bang, Boo-Hyoung
    Kim, Min-Woo
    James, Scott C.
    Yarin, Alexander L.
    Yoon, Sam S.
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 135 : 604 - 613
  • [2] Stairwell smoke transport in a full-scale high-rise building: Influence of opening location
    He, Junjiang
    Huang, Xinyan
    Ning, Xiaoyao
    Zhou, Tiannian
    Wang, Jian
    Yuen, Richard
    FIRE SAFETY JOURNAL, 2020, 117
  • [3] Investigation on Smoke Flow in Stairwells induced by an Adjacent Compartment Fire in High Rise Buildings
    Zhang, Jun
    Weng, Jingwen
    Zhou, Tiannian
    Ouyang, Dongxu
    Chen, Qinpei
    Wei, Ruichao
    Wang, Jian
    APPLIED SCIENCES-BASEL, 2019, 9 (07):
  • [4] Theoretical and numerical study of smoke acceleration effect in the U shaped shaft of a high-rise building
    Li, Man
    Shen, Yize
    Zhang, Zhiyuan
    Ji, Jie
    Gao, Zihe
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2024, 203
  • [5] Experimental and numerical investigation of smoke dynamics in vertical cylinders and open-air environment
    Ahn, Chan-Sol
    Park, Chan-Woo
    Kim, Min-Woo
    Kim, Tae-Gun
    James, Scott C.
    Yoon, Youngbin
    Yarin, Alexander L.
    Yoon, Sam S.
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 135 : 985 - 995
  • [6] Dimensionless analytical solutions for steady-state fire smoke spread through high-rise shaft
    Qi, Dahai
    Wang, Liangzhu
    Ji, Jie
    Li, Man
    FIRE SAFETY JOURNAL, 2017, 93 : 12 - 20
  • [7] Numerical Simulation of Smoke Diffusion in High-Rise Building Fires
    Xu Xiaolei
    He Jiapeng
    Zhou Ru
    Jing Chengyin
    PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL VII, PTS A AND B, 2008, 7 : 713 - 716
  • [8] Modelling fire smoke dynamics in a stairwell of high-rise building: Effect of ambient pressure
    He, Junjiang
    Huang, Xinyan
    Ning, Xiaoyao
    Zhou, Tiannian
    Wang, Jian
    Yuen, Richard Kwok Kit
    CASE STUDIES IN THERMAL ENGINEERING, 2022, 32
  • [9] Numerical Investigation of the Wind and Thermal Conditions in Sky Gardens in High-Rise Buildings
    Mohammadi, Murtaza
    Calautit, John Kaiser
    ENERGIES, 2019, 12 (07)
  • [10] Study on Smoke Control Strategy in a High-rise Building Fire
    Yu, Yuan
    Chu, Yan-yan
    Liang, Dong
    2013 INTERNATIONAL CONFERENCE ON PERFORMANCE-BASED FIRE AND FIRE PROTECTION ENGINEERING (ICPFFPE 2013), 2014, 71 : 145 - 152