Double synchronous reference frame PLL for power converters control

被引:68
作者
Rodríguez, P [1 ]
Pou, J [1 ]
Bergas, J [1 ]
Candela, I [1 ]
Burgos, R [1 ]
Boroyevich, D [1 ]
机构
[1] Tech Univ Catalonia, Dept Elect & Elect Engn, Power Qual & Renewable Energy QuPER, EUETIT, Terrassa 08222, Spain
来源
2005 IEEE 36TH POWER ELECTRONIC SPECIALISTS CONFERENCE (PESC), VOLS 1-3 | 2005年
关键词
D O I
10.1109/PESC.2005.1581815
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper deals with one of the most important issues in the control of grid-connected converters, which is the detection of the positive sequence fundamental component of the utility voltage. The study carried out in this paper conducts to a fast, precise, and robust positive sequence voltage detector offering a good behavior, even if unbalanced and distorted conditions are present in the grid. The proposed detector utilizes a new "Double Synchronous Reference Frame PLL" (DSRF-PLL), which completely eliminates the existing errors in conventional synchronous reference frame PILL systems (SRF-PLL) when operating under unbalanced utility voltages. In the study performed in this paper, the positive and negative sequence components of the unbalanced voltage vector are properly characterized. When this unbalanced vector is expressed on the DSRF, the analysis of the signals on the DSRF axes permits to design a decoupling network which isolates the positive and negative sequence components. This decoupling network gives rise to a new PLL structure which detects the positive sequence voltage component quickly and accurately. In this paper, conclusions of the analytical study are verified by simulation and experiment.
引用
收藏
页码:1415 / 1421
页数:7
相关论文
共 10 条
[1]  
Arruda LN, 2001, IEEE IND APPLIC SOC, P2655, DOI 10.1109/IAS.2001.955993
[2]   A phase tracking system for three phase utility interface inverters [J].
Chung, SK .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2000, 15 (03) :431-438
[3]   Active filtering function of three-phase PWM boost rectifier under different line voltage conditions [J].
Cichowlas, M ;
Malinowski, M ;
Kazmierkowski, MP ;
Sobczuk, DL ;
Rodríguez, P ;
Pou, J .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2005, 52 (02) :410-419
[4]  
Ghosh A., 2002, IEEE Power Engineering Review, V22, P63, DOI 10.1109/39.975663
[5]   A method for synchronization of power electronic converters in polluted and variable-frequency environments [J].
Karimi-Ghartemani, M ;
Iravani, MR .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2004, 19 (03) :1263-1270
[6]   Operation of a phase locked loop system under distorted utility conditions [J].
Kaura, V ;
Blasko, V .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (01) :58-63
[7]  
Lee S. J., 1999, P IND APPL C 34 IAS, V4, P2167
[8]  
Rodríguez P, 2002, INT C HARMON QUAL PO, P614
[9]  
SONG HS, 1999, POW EL SPEC C PESC 9, V1, P533
[10]   Flexible control of small wind turbines with grid failure detection operating in stand-alone and grid-connected mode [J].
Teodorescu, R ;
Blaabjerg, F .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2004, 19 (05) :1323-1332