The experimental verification on the optimal discharge pressure in a subcooler-based transcritical CO2 system for space heating

被引:36
作者
Song, Yulong [1 ]
Ye, Zuliang [1 ]
Wang, Yikai [1 ]
Cao, Feng [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Xian 710049, Shaanxi, Peoples R China
关键词
Transcritical CO2 system; Space heating; Discharge pressure; Optimization; Experimental verification; COMPRESSION REFRIGERATION SYSTEM; PUMP WATER-HEATER; COMBINED R134A; PERFORMANCE; TEMPERATURE; CYCLE; OPTIMIZATION; PLANT;
D O I
10.1016/j.enbuild.2017.11.015
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
To analyze the evaluation of the optimal discharge pressure in subcooler-based transcritical CO2 system, a prototype was tested under various working conditions. Experimental data showed that the power consumption increased while the heating capacity increased first and then kept unchanged even decreased with CO2 discharge pressure increased. Thus, COP increased first and then decreased, which verified the existence of the optimal discharge pressure in the subcooler-based system. The water temperature in CO2 gas-cooler exit rose obviously while that in R134a condenser exit reduced with discharge pressure increased. Besides, the optimal discharge pressure decreased with the decline in air temperature, water return temperature and water delivery temperature among the testing range. Comparing with the optimal discharge pressure in the single used transcritical CO2 system, the optimal value in the subcooler-based system was much higher, and the difference between the two pressures decreased with the air temperature decreased. (C) 2017 Elsevier B.V. All rights reserved.
引用
收藏
页码:1442 / 1449
页数:8
相关论文
共 50 条
[11]   Optimal discharge pressure in transcritical CO2 heat pump water heater with internal heat exchanger based on pinch point analysis [J].
Ye, Zuliang ;
Wang, Yikai ;
Song, Yulong ;
Yin, Xiang ;
Cao, Feng .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 118 :12-20
[12]   Conventional and advanced exergy analyses of transcritical CO2 ejector refrigeration system equipped with thermoelectric subcooler [J].
Liu, Xi ;
Yu, Kaihong ;
Wan, Xinchen ;
Zheng, Minfeng ;
Li, Xuelai .
ENERGY REPORTS, 2021, 7 :1765-1779
[13]   Effect of dedicated mechanical subcooler size and gas cooler pressure control on transcritical CO2 booster systems [J].
D'Agaro, P. ;
Coppola, M. A. ;
Cortella, G. .
APPLIED THERMAL ENGINEERING, 2021, 182
[14]   Experimental assessment of a thermoelectric subcooler included in a transcritical CO2 refrigeration plant [J].
Aranguren, P. ;
Sanchez, D. ;
Casi, A. ;
Cabello, R. ;
Astrain, D. .
APPLIED THERMAL ENGINEERING, 2021, 190
[15]   Constrained optimal high pressure equation of CO2 transcritical cycle [J].
Shao, Liang-Liang ;
Zhang, Zi-Yang ;
Zhang, Chun-Lu .
APPLIED THERMAL ENGINEERING, 2018, 128 :173-178
[16]   Experimental studies on transcritical CO2 heat pump system for simultaneous water cooling and heating application [J].
Date, Abhijit ;
Patil, Omprakash ;
Shet, Shrikant A. ;
Agrawal, Neeraj .
INTERNATIONAL JOURNAL OF GREEN ENERGY, 2022, 19 (02) :201-209
[17]   Experimental evaluation of a transcritical CO2 refrigeration facility working with an internal heat exchanger and a thermoelectric subcooler: Performance assessment and comparative [J].
Casi, Alvaro ;
Aranguren, Patricia ;
Araiz, Miguel ;
Sanchez, Daniel ;
Cabello, Ramon ;
Astrain, David .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2022, 141 :66-75
[18]   Experimental and theoretical analysis of the optimal high pressure and peak performance coefficient in transcritical CO2 heat pump [J].
Qin, Xiang ;
Zhang, Fan ;
Zhang, Dongwei ;
Gao, Zhao ;
Tang, Songzhen .
APPLIED THERMAL ENGINEERING, 2022, 210
[19]   Comprehensive experimental study on a transcritical CO2 ejector-expansion refrigeration system [J].
Zhu, Yinhai ;
Li, Conghui ;
Zhang, Fuzhen ;
Jiang, Pei-Xue .
ENERGY CONVERSION AND MANAGEMENT, 2017, 151 :98-106
[20]   Investigation of the optimal intermediate water temperature in a combined r134a and transcritical CO2 heat pump for space heating [J].
Song, Yulong ;
Li, Dongzhe ;
Cao, Feng ;
Wang, Xiaolin .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 79 :10-24