Thermal characteristics of a multichip module using PF-5060 and water

被引:8
作者
Choi, M [1 ]
Cho, K
机构
[1] Sungkyunkwan Univ, Grad Sch, Sch Mech Engn, Suwon, South Korea
[2] Sungkyunkwan Univ, Sch Mech Engn, Suwon, South Korea
来源
KSME INTERNATIONAL JOURNAL | 1999年 / 13卷 / 05期
关键词
multichip module; rectangular channel; modified Blasius equation; heat transfer coefficient; Nusselt number;
D O I
10.1007/BF02939332
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
The experiments were performed by using PF-5060 and water to investigate the thermal characteristics from an in-line 6X1 array of discrete heat sources for simulating the multichip module which were flush mounted on the top wall of a horizontal, rectangular channel of aspect ratio 0.2. The inlet temperature was 15 degrees C for all experiments, and the parameters were the heat flux of simulated VLSI chips with 10, 20, 30, and 40W/cm(2) and the Reynolds numbers ranging from 3,000 to 20,000. The measured friction factors for PF-5060 and water gave a good agreement with the values predicted by the modified Blasius equation within +/-6%. The chip surface temperatures for water were lower by 14.4 similar to 21.5 degrees C than those for PF-5060 at the heat flux of 30W/cm(2). From the boiling curve of PF-5060, the temperature overshoot at the first heater was 3.5 degrees C and was 2.6 degrees C at the sixth heater. The local heat transfer coefficients for water were larger by 5.5 similar to 11.2% than those for PF-5060 at the heat flux of 30W/cm2, and the local heat transfer coefficients for PF-5060 and water reached a uniform value after the fourth row. This meant that the thermally fully developed condition was reached after the fourth row. The local Nusselt number data gave the best agreement with the values predicted by the Malina and Sparrow's correlation and the empirical correlations for Nusselt number were provided at the first, fourth and sixth rows for a channel Reynolds number over 3,000.
引用
收藏
页码:443 / 450
页数:8
相关论文
共 18 条