Diagnosis of On-Load Tap Changer (OLTC) Using Dynamic Resistance Measurement

被引:0
|
作者
Aziz, Mohd Azhar Abdul [1 ]
Talib, Mohd Aizam [1 ]
Arumugam, Ragavan [1 ]
机构
[1] TNB Res Sdn Bhd, Kajang 43000, Selangor, Malaysia
来源
2014 IEEE 8TH INTERNATIONAL POWER ENGINEERING AND OPTIMIZATION CONFERENCE (PEOCO) | 2014年
关键词
On Load Tap Changer; Dynamic Resistance; Transformer Diagnostic;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
On Load Tap Changer (OLTC) is one of the important and most expensive sub-components in a power transformer. The fail operation of OLTC can cause catastrophic failure of in-service power transformers. Proper and adequate maintenance conducted on serviced aged OLTC can reduce the unexpected unavailability and failure rate of power transformer. Nowadays, several off-line and on-line diagnostic techniques have been used to diagnose the condition of load tap changer. These diagnostic results are important to determine the required maintenance on OLTC. In this paper, the condition of OLTC on in-service transformer was assessed using the dynamic resistance measurement. The results from new unit of OLTC installed in power transformer at the factory and on serviced aged OLTC were presented. The findings suggested that the technique is very promising in detecting problem associated with the contact wear and early stage of contact degradation in OLTC.
引用
收藏
页码:494 / 497
页数:4
相关论文
共 50 条
  • [1] On-load tap changer diagnosis with dynamic resistance measurements
    Jongen, Rogier
    Seitz, Paul P.
    Strehl, Thomas
    Smit, Johan
    Leich, Rory
    Gulski, Edward
    PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 485 - 488
  • [2] On-load Tap Changer Diagnosis: Interpretation of Dynamic Resistance Deviations
    Erbrink, J. J.
    Gulski, E.
    Smit, J. J.
    Leich, R.
    Seitz, P. P.
    Quak, B.
    CONFERENCE RECORD OF THE 2010 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION (ISEI), 2010,
  • [3] On-Load Tap Changer's Dynamic Resistance Measurement Settings and Interpretation
    Erbrink, J. J.
    Aditya, J.
    Chmura, L. A.
    Smit, J. J.
    Leich, R.
    Quak, B.
    2011 ELECTRICAL INSULATION CONFERENCE (EIC), 2011, : 54 - 58
  • [4] Acoustic emission signal analysis of On-Load Tap Changer (OLTC)
    Shanker, T. Bhavani
    Nagamani, H. N.
    Punekar, Gururaj S.
    2013 IEEE 1ST INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON), 2013, : 347 - 352
  • [5] ON-LOAD TAP CHANGER (OLTC) SELECTION AND OPTIMIZATION IN LARGE POWER TRANSFORMERS
    Nambi, Shankar
    Kumar, Mohit
    Veeran, Kannan
    John, John K.
    2024 IEEE IAS PETROLEUM AND CHEMICAL INDUSTRY TECHNICAL CONFERENCE, PCIC, 2024, : 427 - 435
  • [6] Fast Fault Diagnosis of On-Load Tap Changer (OLTC) Based on Feature Importance and KNN Classifier
    Zhou, Hongwei
    Cui, Ming
    Dong, Tian
    Liu, Fu
    Yuan, Dongyue
    2015 INTERNATIONAL CONFERENCE ON INFORMATION SCIENCE AND INTELLIGENT CONTROL (ISIC 2015), 2015, : 12 - 16
  • [7] Application vibroacoustic in the diagnosis of on-load tap changer
    Raclaw, Marcin
    Gielniak, Jaroslaw
    PRZEGLAD ELEKTROTECHNICZNY, 2018, 94 (10): : 126 - 129
  • [8] Methods of diagnosis of for failures power On-load tap changer
    Rivas Trujillo, Edwin
    Carlos Burgos, Juan
    Garcia Prada, Juan Carlos
    INGENIERIA, 2007, 12 (02): : 68 - 72
  • [9] Measurement Method for the Transition Resistance of On-load Tap Changer Based on Signal Processing
    Song D.
    Ding L.
    Dong B.
    Ma Y.
    Liu X.
    Song, Dongdong (mapex_dongdong@126.com), 2020, Science Press (46): : 922 - 930
  • [10] Analysis of Vibration Signal for Power Transformer On-Load Tap Changer (OLTC) Condition Monitoring
    Seo, Junhyuck
    Ma, Hui
    Saha, Tapan K.
    2018 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2018,