Experimental investigation on a desiccant dehumidification unit using fin-tube heat exchanger with silica gel coating

被引:107
作者
Zhao, Y. [1 ]
Ge, T. S. [1 ]
Dai, Y. J. [1 ]
Wang, R. Z. [1 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, MOE China, Shanghai Key Lab Power Mech Engn, Shanghai 200240, Peoples R China
关键词
Desiccant dehumidification unit; Desiccant coated heat exchanger; Low grade thermal energy; Experimental investigation; COOLING SYSTEM; PERFORMANCE;
D O I
10.1016/j.applthermaleng.2013.10.018
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper, an experimental setup of a desiccant dehumidification unit silica gel coated fin-tube heat exchanger is installed and investigated. In this unit, two silica gel coated heat exchangers (SCHE) are adopted and switched to provide continuous dehumidification capacity. Meanwhile, hot water from vacuum tube solar collector is used to regenerate silica gel. System performance is evaluated in terms of moisture removal mass and thermal COP. Influences of major parameters on system performance are tested and analyzed under Shanghai summer conditions. It is found that system performance is affected significantly by cycle time between dehumidification and regeneration, and optimal cycle time is 600 s under test conditions. For actual system, the unit can be independently used as dehumidifier with 100% fresh air under mild conditions. But when the outside humidity is too large, it can be used in combination with primary return air-conditioning to provide satisfied supply air. (C) 2013 Published by Elsevier Ltd.
引用
收藏
页码:52 / 58
页数:7
相关论文
共 19 条
[1]   Field performance measurements of a heat pump desiccant unit in dehumidification mode [J].
Aynur, T. N. ;
Hwang, Y. H. ;
Radermacher, R. .
ENERGY AND BUILDINGS, 2008, 40 (12) :2141-2147
[2]   An experimental study of structured packing dehumidifier/regenerator operating with liquid desiccant [J].
Bassuoni, M. M. .
ENERGY, 2011, 36 (05) :2628-2638
[3]   Parameter analysis to improve rotary desiccant dehumidification using a mathematical modes [J].
Dai, YJ ;
Wang, RZ ;
Zhang, HF .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2001, 40 (04) :400-408
[4]   Operational experiences with solar air collector driven desiccant cooling systems [J].
Eicker, Ursula ;
Schneider, Dietrich ;
Schumacher, Juergen ;
Ge, Tianshu ;
Dai, Yanjun .
APPLIED ENERGY, 2010, 87 (12) :3735-3747
[5]   Simulation investigation on solar powered desiccant coated heat exchanger cooling system [J].
Ge, T. S. ;
Dai, Y. J. ;
Li, Y. ;
Wang, R. Z. .
APPLIED ENERGY, 2012, 93 :532-540
[6]   Performance study of silica gel coated fin-tube heat exchanger cooling system based on a developed mathematical model [J].
Ge, T. S. ;
Dai, Y. J. ;
Wang, R. Z. .
ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (06) :2329-2338
[7]   Experimental comparison and analysis on silica gel and polymer coated fin-tube heat exchangers [J].
Ge, T. S. ;
Dai, Y. J. ;
Wang, R. Z. ;
Peng, Z. Z. .
ENERGY, 2010, 35 (07) :2893-2900
[8]   Performance investigation on a novel two-stage solar driven rotary desiccant cooling system using composite desiccant materials [J].
Ge, T. S. ;
Li, Y. ;
Dai, Y. J. ;
Wang, R. Z. .
SOLAR ENERGY, 2010, 84 (02) :157-159
[9]   Sorption characteristics of honeycomb-type sorption element composed of organic sorbent [J].
Inaba, H ;
Kida, T ;
Horibe, A ;
Kaneda, M .
JSME INTERNATIONAL JOURNAL SERIES B-FLUIDS AND THERMAL ENGINEERING, 2002, 45 (01) :183-191
[10]   Use of compound desiccant to develop high performance desiccant cooling system [J].
Jia, C. X. ;
Dai, Y. J. ;
Wu, J. Y. ;
Wang, R. Z. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (02) :345-353