Surface roughness effects on the corona discharge intensity of long-term operating conductors

被引:35
作者
Bian, X. M. [1 ]
Chen, L. [1 ]
Yu, D. M. [1 ]
Wang, L. M. [1 ]
Guan, Z. C. [1 ]
机构
[1] Tsinghua Univ, Grad Sch Shenzhen, Shenzhen 518055, Peoples R China
关键词
NEGATIVE CORONA; LINE; AIR;
D O I
10.1063/1.4764016
中图分类号
O59 [应用物理学];
学科分类号
摘要
An investigation into the effect of surface roughness on corona discharge intensity of long-term operating conductors is presented. The electric field distortion level was found to increase linearly with surface average roughness R-a. At the corona inception voltages, the ionization intensity xi in the ionization zone was calculated, it would increase exponentially with the raise of R-a. As a result, the corona discharge intensity of long-term operating conductors was stronger, and the corona inception voltages were lower than those of the new conductors. The deviation of radio noise and audible noise was found to increase linearly with the raise of R-a. (C) 2012 American Institute of Physics. [http://dx.doi.org/10.1063/1.4764016]
引用
收藏
页数:4
相关论文
共 17 条
[1]   Impact of Surface Roughness on Corona Discharge for 30-year Operating Conductors in 500-kV ac Power Transmission Line [J].
Bian, Xingming ;
Chen, Lan ;
Yu, Deming ;
Wang, Liming ;
Guan, Zhicheng .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (03) :1693-1695
[2]   Influence of Aged Conductor Surface Conditions on AC Corona Discharge With a Corona Cage [J].
Bian, Xingming ;
Yu, Deming ;
Chen, Lan ;
MacAlpine, J. M. K. ;
Wang, Liming ;
Guan, Zhicheng ;
Chen, Fangdong .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (03) :809-818
[3]   Negative Corona Inception Voltages in Rod-plane Gaps at Various Air Pressures and Humidities [J].
Bian, Xingming ;
Meng, Xiaobo ;
Wang, Liming ;
MacAlpine, J. M. K. ;
Guan, Zhicheng ;
Hui, Jianfeng .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (02) :613-619
[4]   Impact of electromagnetic radiation on cascaded failure in high voltage insulators [J].
Bojovschi, A. ;
Wong, K. L. ;
Rowe, W. S. T. .
APPLIED PHYSICS LETTERS, 2011, 98 (05)
[5]   The influence of hanging water droplets on discharge activity, application to high voltage insulators [J].
Bojovschi, A. ;
Rowe, W. S. T. ;
Wong, K. L. .
APPLIED PHYSICS LETTERS, 2011, 98 (09)
[6]   NATURAL AGING OF NON-ENERGIZED ALUMINUM CONDUCTORS [J].
BOOKER, JR .
IEEE TRANSACTIONS ON POWER DELIVERY, 1986, 1 (04) :269-274
[7]   AUDIBLE NOISE PERFORMANCE OF REGULAR AND ASYMMETRIC BUNDLES AND EFFECT OF CONDUCTOR AGING ON PROJECT UHVS 3-PHASE TEST LINE [J].
COMBER, MG ;
NIGBOR, RJ .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1979, 98 (02) :561-572
[8]   Onset voltage of negative corona on dielectric-coated electrodes in air [J].
El-Bahy, MM ;
El-Ata, MAA .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2005, 38 (18) :3403-3411
[9]  
Laforest J. J., 1962, T AM I ELECT ENG, V81, P424
[10]   Onset corona fields and electrical breakdown criteria [J].
Lowke, JJ ;
D'Alessandro, F .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2003, 36 (21) :2673-2682