High-Resistance Grounded Power-System Equivalent Circuit Damage at the Line-Ground Fault Location-Part II

被引:11
作者
Paul, Dev [1 ]
Sutherland, Peter E. [2 ]
机构
[1] AECOM Technol Corp, Oakland, CA 94612 USA
[2] GE Energy Serv, Schenectady, NY 12345 USA
关键词
Arcing fault; fault resistance; ground fault protection relay; high-resistance grounded (HRG) system; system charging current; MULTIPLE GENERATOR INSTALLATIONS; MEDIUM-VOLTAGE INDUSTRIAL; PROTECTION;
D O I
10.1109/TIA.2014.2346691
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper provides the electrical equivalent circuits of high-resistance grounded (HRG) power systems other than the delta-wye-connected utility power supply transformer included in Part I of this paper. This paper also provides the HRG of a medium-voltage generator for connection to an industrial power system and to a utility power system, and this paper discusses a line-ground fault with fault resistance. Three-line diagrams of ungrounded power systems are also included to illustrate the HRG application and its effect on the ground fault current during the line-ground fault. The damage at the fault location is based on the assumption that the fault remains a line-ground fault until it is cleared by appropriate ground fault protection relays. The fault resistance and the fault current that have an effect on the damage at the fault location are included. This paper provides guidance to update the current edition of the IEEE STD. 142, with respect to HRG systems.
引用
收藏
页码:4188 / 4196
页数:9
相关论文
共 18 条
[1]  
[Anonymous], 1964, EL TRANSM DISTR REF
[2]   CHARGING CURRENT DATA FOR GUESSWORK-FREE DESIGN OF HIGH-RESISTANCE GROUNDED SYSTEMS [J].
BAKER, DS .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1979, 15 (02) :136-140
[3]  
Beeman D., 1955, IND POWER SYSTEMS HD
[4]   13.8-kV Selective High-Resistance Grounding System for a Geothermal Generating Plant-A Case Study [J].
Das, J. C. ;
Perich, Edmundo .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2013, 49 (03) :1234-1243
[5]  
Dunki-Jacobs J.R., 2007, IND POWER SYSTEM GRO
[6]   GROUND FAULT TESTS ON HIGH-RESISTANCE GROUNDED 13.8-KV ELECTRICAL DISTRIBUTION SYSTEM OF MODERN LARGE CHEMICAL-PLANT .1. [J].
FOX, FK ;
MCCLUNG, LB .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1974, IA10 (05) :581-600
[7]  
*IEEE, 1993, C37101 IEEE
[8]  
*IEEE, 1982, 1421982 IEEE
[9]  
Kingrey Lawrence J., 2010, P PCIC C SAN ANT TX, P31
[10]   GROUND FAULT TESTS ON HIGH-RESISTANCE GROUNDED 13.8-KV ELECTRICAL DISTRIBUTION SYSTEM OF MODERN LARGE CHEMICAL-PLANT .2. [J].
MCCLUNG, LB ;
WHITTINGTON, BW .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1974, IA10 (05) :601-617