Energy and economic analysis of the bypass method for the computer room air conditioning units of a small data center

被引:0
作者
Erden, Hamza Salih [1 ]
Turkmen, Ismail [2 ]
机构
[1] Istanbul Tech Univ, Inst Informat, Dept Informat Applicat, TR-34469 Istanbul, Turkey
[2] Yildiz Tech Univ, Fac Engn, Dept Mech Engn, TR-34349 Istanbul, Turkey
来源
JOURNAL OF THE FACULTY OF ENGINEERING AND ARCHITECTURE OF GAZI UNIVERSITY | 2022年 / 37卷 / 04期
关键词
Energy efficiency; data centers; cooling infrastructure; economics; modeling & optimization; INDUCED CRAH BYPASS; OPTIMIZATION; PERFORMANCE; COST;
D O I
10.17341/gazimmfd.897270
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Earlier optimization studies utilized reduced-order modeling approach combining flow network modeling at room level and thermodynamic modeling at the cooling infrastructure level to investigate the energy saving potential of the computer room air handling (CRAH) bypass (BP) method for data centers. Flow network modeling worked well in predicting the cooling infrastructure power use at various BP fractions. While existing studies are either on hypothetical data centers or experimental setups, there is no considerable work on the feasibility of the method in real and operational data center. Economic requirements of the method is another aspect missing in the literature. This study includes assessments on the feasibility of the CRAH BP methods (forced and induced) in an operational data center using reduced-order modeling approaches suggested in the literature. As a result of the energy and economic analysis of various scenarios, it has been concluded that the feasibility of the CRAH BP method is directly related to the number of fans required by the design and recommendations for application have been proposed.
引用
收藏
页码:1883 / 1898
页数:16
相关论文
共 49 条
  • [1] Investigation of CRAH Bypass for Air-Cooled Data Centers using Computational Fluid Dynamics
    Ahmadi, Vahid Ebrahimpour
    Erden, Hamza Salih
    [J]. 2018 IEEE INTERNATIONAL TELECOMMUNICATIONS ENERGY CONFERENCE (INTELEC), 2018,
  • [2] A parametric CFD study of computer room air handling bypass in air-cooled data centers
    Ahmadi, Vahid Ebrahimpour
    Erden, Hamza Salih
    [J]. APPLIED THERMAL ENGINEERING, 2020, 166
  • [3] Effect of envelope insulation on building heating energy requirement, cost and carbon footprint from a life-cycle perspective
    Altun, Murat
    Akgul, Cagla Meral
    Akcamete, Asli
    [J]. JOURNAL OF THE FACULTY OF ENGINEERING AND ARCHITECTURE OF GAZI UNIVERSITY, 2020, 35 (01): : 147 - 163
  • [4] [Anonymous], 2020, STULZ SENAY UNER KEY
  • [5] ASHRAE, 2001, FUND HDB
  • [6] ASHRAE, 2015, OWN OP COSTS HVAC AP
  • [7] ASHRAE, 2009, DES CONS DAT EQ CTR, Vsecond
  • [8] ASHRAE, 2015, THERM GUID DAT PROC
  • [9] Experimentally Validated Computational Fluid Dynamics Model for Data Center With Active Tiles
    Athavale, Jayati
    Joshi, Yogendra
    Yoda, Minami
    [J]. JOURNAL OF ELECTRONIC PACKAGING, 2018, 140 (01)
  • [10] Belady C., 2008, 6 GREEN GRID DAT CTR