Performance investigation and numerical evaluation of a single-effect double-lift absorption chiller

被引:11
|
作者
Saoud, Abdelmajid [1 ]
Bruno, Joan Carles [2 ]
Boukhchanaa, Yasmina [1 ]
Fellah, Ali [3 ]
机构
[1] Univ Gabes, Natl Sch Engineers Gabes, Lab Appl Thermodynam, LR18ES33, Gabes 6029, Tunisia
[2] Univ Rovira I Virgili, Mech Engn Dept, CREVER Res Grp Appl Thermal Engn, Ave Paisos Catalans 26, Tarragona 43007, Spain
[3] Univ Gabes, Higher Inst Appl Sci & Technol Gabes, Lab Appl Thermodynam LR18ES33, Gabes 6029, Tunisia
关键词
Single-effect double-lift absorption chiller (SE-DL AC); Refrigeration; Coefficient of Performance (COP); Thermodynamic analysis; Glide temperature(?T); Energy efficiency; REFRIGERATION SYSTEM; COOLING SYSTEMS; EXERGY ANALYSIS; SOLAR-ENERGY; LICL-H2O; INVERSE; DRIVEN;
D O I
10.1016/j.applthermaleng.2023.120369
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study deals with innovative integrated absorption refrigeration systems. This cycle could be useful for converting low-temperature energy sources into useful outputs like cooling. The Single Effect Double Lift Ab-sorption Chiller (SE-DL AC) was introduced and energetically evaluated. A detailed modeling based on the first law of thermodynamics is built to investigate the performance of this novel system. This model was initially validated considering a reference SE-DL AC from the Hitachi company with a nominal cooling capacity of 106.1 kW. This system is compared to a conventional single-effect absorption chiller while maintaining the same operating parameters and boundary conditions in both configurations to ensure a fair comparison in terms of the internal and external baseline operating conditions. A parametric study of the driving hot water inlet temper-ature, the solution mass flow rate, the effectiveness of the solution heat exchanger, and internal and external temperatures on the Coefficient of Performance (COP), Cooling capacity (CC), and Glide Temperature (Delta T) are conducted. The final results demonstrate that the cooling production capability of the SE-DL is increased by an average of about tenfold when compared to the conventional SE AC at a thermal source temperature of 88.7 degrees C and an inlet hot water mass flow rate of 1 kg/s. The COP results produced under the same operating conditions are quite similar. The cooling generation capability of the SEDL is, on average, 10 times greater than that of the traditional SE AC. This explains that the SEDL-AC is well suited for a wide range of low-temperature heat sources (e.g., solar energy). Furthermore, the SE-DL AC enables efficient use of low-grade heat with a high glide tem-perature in the driving heat stream of about 10 times (36 degrees C instead of 3.5 degrees C). This large temperature difference exemplifies that the SE-DL AC absorption chiller is an alternative for extracting as much heat as possible, thereby improving cold production.
引用
收藏
页数:13
相关论文
共 50 条
  • [11] Energy, exergy, economic analysis and optimization of single-effect absorption chiller network
    F. Panahizadeh
    M. Hamzehei
    M. Farzaneh-Gord
    A. A. V. Ochoa
    Journal of Thermal Analysis and Calorimetry, 2021, 145 : 669 - 699
  • [12] Space cooling using geothermal single-effect water/lithium bromide absorption chiller
    El Haj Assad, Mamdouh
    Sadeghzadeh, Milad
    Ahmadi, Mohammad Hossein
    Al-Shabi, Mohammad
    Albawab, Mona
    Anvari-Moghaddam, Amjad
    Bani Hani, Ehab
    ENERGY SCIENCE & ENGINEERING, 2021, 9 (10) : 1747 - 1760
  • [13] PERFORMANCE ANALYSIS FOR THE CHARACTERISTICS OF DOUBLE/SINGLE EFFECT HYBRID TYPE ABSORPTION CHILLER
    Park, Chan Woo
    You, Da Young
    Kim, Hyoung Jin
    Im, Ik-Tae
    INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2010, 18 (01) : 23 - 29
  • [14] Experimental performance of a double-lift absorption heat transformer for manufacturing-process steam generation
    Lubis, Arnas
    Giannetti, Niccolo
    Yamaguchi, Seiichi
    Saito, Kiyoshi
    Inoue, Naoyuki
    ENERGY CONVERSION AND MANAGEMENT, 2017, 148 : 267 - 278
  • [15] Experimental results of a double-lift compression-absorption heat pump
    Ziegler, F.
    Haemmer, G.
    Proceedings of the International Conference on Applications and Efficiency of Heat Pump Systems, 1991,
  • [16] Performance assessment of an integrated free cooling and solar powered single-effect lithium bromide-water absorption chiller
    Ali, Ahmed Hamza H.
    Noeres, Peter
    Pollerberg, Clemens
    SOLAR ENERGY, 2008, 82 (11) : 1021 - 1030
  • [17] A New Single-Effect Hot-Water Absorption Chiller Air Conditioner using Solar Energy
    Ha, Q. P.
    Vakiloroaya, Vahid
    2013 AUSTRALASIAN UNIVERSITIES POWER ENGINEERING CONFERENCE (AUPEC), 2013,
  • [18] Thermodynamic investigation of an innovative solar-driven trigeneration plant based on an integrated ORC-single effect-double lift absorption chiller
    Saoud, Abdelmajid
    Boukhchana, Yasmina
    Bruno, Joan Carles
    Fellah, Ali
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2024, 50
  • [19] Performance assessment of a double-lift absorption prototype for low temperature refrigeration driven by low-grade heat
    Toppi, Tommaso
    Aprile, Marcello
    Guerra, Marco
    Motta, Mario
    ENERGY, 2017, 125 : 287 - 296
  • [20] SINGLE-DOUBLE-EFFECT ABSORPTION CHILLER PERFORMANCE BY ADJUSTING THE COMBINATION OF THE SOLUTION MASS FLOW RATES
    Arnas
    Jeong, Jongsoo
    Saito, Kiyoshi
    Yabase, Hajime
    Alhamid, M. Idrus
    Nasruddin
    5TH IIR INTERNATIONAL CONFERENCE ON THERMOPHYSICAL PROPERTIES AND TRANSFER PROCESSES OF REFRIGERANTS (TPTPR), 2017, : 1138 - 1145