EXPERIMENTAL STUDY TO EVALUATE EFFECT OF SOURCE TEMPERATURE ON COP AND COMPRESSOR STATUS IN WATER-TO-AIR HEAT PUMPS

被引:6
作者
Ceviz, Mehmet Akif [1 ]
Afshari, Faraz [1 ]
Ceylan, Murat [1 ]
Muratcobanoglu, Burak [1 ]
Mandev, Emre [1 ]
Gelen, Gokhan [1 ]
机构
[1] Erzurum Tech Univ, Dept Mech Engn, Erzurum, Turkiye
关键词
heat pump; coefficient of performance; compressor power consumption; efficiency; enthalpy uncertainties; PERFORMANCE EVALUATION; SYSTEM; OPTIMIZATION; CHARGE;
D O I
10.1615/HeatTransRes.2023048436
中图分类号
O414.1 [热力学];
学科分类号
摘要
Heat pump devices have been researched and analyzed from different aspects, which indicates the importance of these devices. In fact, these devices transfer heat energy effectively from one source to another by consuming power. In this work, the importance of source temperature and its effect on system performance and compressor status has been investigated. It is shown that if the temperature of the heat source is low, the refrigerant at the inlet of the compressor will be in the two-phase region, which could cause damage to the compressor. In these cases, the evaporator design can be changed as available solutions or a high-temperature heat source can be provided in the present study. On the other hand, in the two-phase region, calculating the work of the compressor with enthalpy values will be a problem and may cause a computational error in the power consumption of the compressor. The reason for this is that the enthalpy of refrigerant in the compressor cannot be obtained with two properties, i.e., temperature and pressure. This issue has been considered and the rate of computational error has been obtained. R134a refrigerant was used as circulating gas in the used water-to-air heat pump. The results obtained in the experiments performed showed that the COP value of the heat pump increased by 172% when the source temperature increased from 6 degrees C to 34 degrees C. As the source temperature increases, more energy is transferred to the system. This issue raises both high-pressure and low-pressure values. This increase was recorded as 34% for high pressure and 17% for low pressure when the source temperature increased from 6 degrees C to 34 degrees C.
引用
收藏
页码:51 / 66
页数:16
相关论文
共 41 条
[11]   THERMAL ANALYSIS OF DIFFERENT HEAT PUMP SYSTEMS FOR HEATING PROCESS OF ELECTRIC VEHICLES [J].
Bayram, Halil ;
Sevilgen, Gokhan .
HEAT TRANSFER RESEARCH, 2021, 52 (06) :41-57
[12]   A PCM thermal storage for ground-source heat pumps: simulating the system performance via CFD approach. [J].
Bonamente, Emanuele ;
Aquino, Andrea ;
Cotana, Franco .
71ST CONFERENCE OF THE ITALIAN THERMAL MACHINES ENGINEERING ASSOCIATION (ATI 2016), 2016, 101 :1079-1086
[13]   Performance analysis of a novel air source hybrid solar assisted heat pump [J].
Cai, Jingyong ;
Li, Zhouhang ;
Ji, Jie ;
Zhou, Fan .
RENEWABLE ENERGY, 2019, 139 :1133-1145
[14]   Experimental research on a solar air-source heat pump system with phase change energy storage [J].
Chen, Haifei ;
Wang, Yunjie ;
Li, Jing ;
Cai, Baorui ;
Zhang, Fuwei ;
Lu, Tao ;
Yang, Jie ;
Jiang, Lvlin ;
Zhang, Yang ;
Zhou, Jinzhi .
ENERGY AND BUILDINGS, 2020, 228
[15]   Performance comparison between R22 and R744 solar-geothermal hybrid heat pumps according to heat source conditions [J].
Choi, Jongmin ;
Kang, Byun ;
Cho, Honghyun .
RENEWABLE ENERGY, 2014, 71 :414-424
[16]   Experimental investigation on the thermal performance of a qanat-source heat pump [J].
Delfani, Shahram ;
Esmaeelian, Jafar ;
Karami, Maryam .
GEOTHERMICS, 2021, 89
[17]   A NEW METHOD TO DETERMINE THE THERMAL PROPERTIES OF SOIL FOR VERTICAL-BOREHOLE GROUND-SOURCE HEAT PUMP SYSTEMS [J].
Dong, Xingjie ;
Gu, Bo .
HEAT TRANSFER RESEARCH, 2015, 46 (05) :417-427
[18]   Higher ground source heat pump COP in a residential building through the use of solar thermal collectors [J].
Girard, Aymeric ;
Jadraque Gago, Eulalia ;
Muneer, Tariq ;
Caceres, Gustavo .
RENEWABLE ENERGY, 2015, 80 :26-39
[19]   Experimental investigation on using building shower drain water as a heat source for heat pump systems [J].
Khanlari, Ataollah ;
Sozen, Adnan ;
Sahin, Bayram ;
Di Nicola, Giovanni ;
Afshari, Faraz .
ENERGY SOURCES PART A-RECOVERY UTILIZATION AND ENVIRONMENTAL EFFECTS, 2024, 46 (01) :11965-11977
[20]   Performance enhancement of a greenhouse dryer: Analysis of a cost-effective alternative solar air heater [J].
Khanlari, Ataollah ;
Sozen, Adnan ;
Sirin, Ceylin ;
Tuncer, Azim Dogus ;
Gungor, Afsin .
JOURNAL OF CLEANER PRODUCTION, 2020, 251