Experimental analysis on energy recovery ventilator with latent heat exchanger using hollow fiber membrane

被引:12
作者
Cho, Hye-Jin [1 ]
Cheon, Seong-Yong [1 ]
Jeong, Jae-Weon [1 ]
机构
[1] Hanyang Univ, Coll Engn, Dept Architectural Engn, 222 Wangsimni Ro, Seoul 04763, South Korea
基金
新加坡国家研究基金会;
关键词
Energy recovery ventilator; Hollow fiber membrane; Experimental analysis; Latent heat recovery; Ventilation load reduction; MASS-TRANSFER; FRESH AIR; EFFICIENCY; MOISTURE;
D O I
10.1016/j.enconman.2023.116706
中图分类号
O414.1 [热力学];
学科分类号
摘要
A novel energy recovery ventilation unit with a hollow fiber membrane-based latent heat exchanger is proposed and built to experimentally evaluate its operational performance and energy efficiency. The proposed system consists of a latent heat exchanger fabricated by hollow fiber membrane to accommodate the latent load of introduced outdoor air and a flat-plate sensible heat exchanger to eliminate the sensible load. Annual operating strategies are established based on outdoor air conditions, and experiments are conducted under each operation mode. Further, the thermal behaviors of air (including temperature and humidity) under each operation mode are described according to the measured data. The proposed system exhibits a sensible, latent, and enthalpy effectiveness of 53.6-80.1%, 68.1-73.1%, and 76.1-89.6%, respectively. As for the energy efficiency of the proposed ventilation unit, the coefficients of energy are 29.63 and 15.29 under the summer and winter operation modes, respectively, which meet the minimum energy performance requirements of the local test standard. Finally, the potential reduction in the ventilation load for each operation mode is estimated using the measured data. The proposed unit could reduce the ventilation load by 75.4%and 77.3% in summer and winter operation modes, respectively. These results reveal that the proposed ventilation unit demonstrates significant application potential in improving the operating and energy performance of buildings.
引用
收藏
页数:12
相关论文
共 41 条
[1]  
Air-conditioning Heating and Refrigeration Institute (AHRI), 2020, AIR TO AIR EN REC VE
[2]   Study on recent progress and advances in air-to-air membrane enthalpy exchangers: Materials selection, performance improvement, design optimisation and effects of operating conditions [J].
Albdoor, A. K. ;
Ma, Z. ;
Al-Ghazzawi, F. ;
Arici, M. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2022, 156
[3]  
[Anonymous], 2010, STANDARD 55 2010 THE
[4]  
[Anonymous], JUHUL HEAT EXCHANGER
[5]  
[Anonymous], AHRI AIR TO AIR ENER
[6]  
[Anonymous], 2010, 22010 ASHRAE
[7]  
[Anonymous], 2020, KSB6879
[8]   Membrane-based enthalpy exchangers for coincident sensible and latent heat recovery [J].
Asasian-Kolur, Neda ;
Sharifian, Seyedmehdi ;
Haddadi, Bahram ;
Pourhoseinian, Mohammad ;
Shekarbaghani, Zahra Mousazadeh ;
Harasek, Michael .
ENERGY CONVERSION AND MANAGEMENT, 2022, 253
[9]   Studying the characteristics and energy performance of a composite hollow membrane for air dehumidification [J].
Bui, D. T. ;
Vivekh, P. ;
Islam, M. R. ;
Chua, K. J. .
APPLIED ENERGY, 2022, 306
[10]  
Cho HJ, 2021, PROC ISHVAC, V2021, P24