Experimental Study on Heating Operation Characteristics of a Water Source Heat Pump System of Water-Circuit Reverse Type

被引:0
作者
Kim, Kibong [1 ]
Chang, Kichang [1 ]
Wang, Eunseok [1 ]
Ra, Ho Sang [1 ]
Cho, Junhyun [1 ]
Choi, Bong Su [1 ]
Heo, Jaehyeok [2 ]
Lee, Gilbong [1 ]
机构
[1] Korea Inst Energy Res, Thermal Convers Syst Lab, Daejeon, South Korea
[2] Korea Inst Energy Res, Renewable Heat Integrat Lab, Daejeon, South Korea
关键词
Heating Operation; Low-Temperature River Water; Reverse-Cycle Operation; Water Source Heat Pump;
D O I
10.3795/KSME-B.2023.47.2.071
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
The present study conducted experiment on heating and reverse-cycle operation using a low-temperature heat source. A 20 kW scale water switchable experimental device is built to develop a river water heat pump system with a heat source mix technology that can provide cooling and heating energy irrespective of the temperature characteristics of the heat source. Even at 4 degrees C and 4.5 degrees C, the river water heat pump demonstrates good efficiency, with COPh values of 3.05 and 3.15, respectively. The reverse-cycle operation experiment is conducted using three different methods, switching the water side valve momentarily each time the evaporator's water output temperature reaches -1 degrees C. In the reverse-cycle operation, the inlet and outlet temperatures of the evaporator circulating water are compensated to prevent supercooling of the plate. An optimal operation control pattern to prevent supercooling is determined to be possible through reverse-cycle operation.
引用
收藏
页码:71 / 80
页数:10
相关论文
共 13 条
[1]  
Bae (Heung Hee, 2013, [Korea Journal of Air-Conditioning and Refrigeration Engineering, 설비공학 논문집], V25, P131, DOI 10.6110/KJACR.2013.25.3.131
[2]  
Cho H. M., 2020, STUDY SUPPLY STRATEG, P2
[3]  
Hyun J. J., 2020, STUDY COOLING HEATIN, P6
[4]  
Jung J.-W., 2017, WATER FUTURE, V50, P50
[5]  
박차식, 2009, [Korea Journal of Air-Conditioning and Refrigeration Engineering, 설비공학 논문집], V21, P621
[6]  
K-Water, 2022, WAT INF PORT
[7]  
강동규, 2012, [Korea Journal of Air-Conditioning and Refrigeration Engineering, 설비공학 논문집], V24, P391, DOI 10.6110/KJACR.2012.24.5.391
[8]  
KMA National Climate Data Center, 2022, OP MET DAT PORT
[9]  
Kwon Y., 2022, KOREAN J AIR CONDITI, V34, P163
[10]   Studies on Raw-Water Source Heat Pump Equipped with Thermal Storage Tank in Water Treatment Facility [J].
Oh, Sun Hee ;
Yun, Rin ;
Cho, Yong .
TRANSACTIONS OF THE KOREAN SOCIETY OF MECHANICAL ENGINEERS B, 2013, 37 (05) :467-472