Enhanced AC Fault Ride-through Control for MMC-integrated System Based on Active PCC Voltage Drop

被引:4
作者
Ye, Haihan [1 ]
Chen, Wu [1 ]
Wu, Heng [2 ]
Cao, Wu [1 ]
He, Guoqing [3 ]
Li, Guanghui [3 ]
机构
[1] Southeast Univ, Sch Elect Engn, Ctr Adv Power Convers Technol & Equipment, Nanjing 210096, Peoples R China
[2] Aalborg Univ, Dept Energy Technol, DK-9220 Aalborg, Denmark
[3] China Elect Power Res Inst, Beijing 100192, Peoples R China
关键词
Modular multilevel converter-based high-voltage direct current (MMC-HVDC) system; fault ride-through (FRT); voltage loop saturation; continuous power transmission; point of common coupling (PCC); active voltage drop control; SYNCHRONIZATION STABILITY; GRIDS;
D O I
10.35833/MPCE.2022.000285
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
When a renewable energy station (RES) connects to the rectifier station (RS) of a modular multilevel converter-based high-voltage direct current (MMC-HVDC) system, the voltage at the point of common coupling (PCC) is determined by RS control methods. For example, RS control may become saturated under fault, and causes the RS to change from an equivalent voltage source to an equivalent current source, making fault analysis more complicated. In addition, the grid code of the fault ride-through (FRT) requires the RES to output current according to its terminal voltage. This changes the fault point voltage and leads to RES voltage regulation and current redistribution, resulting in fault response interactions. To address these issues, this study describes how an MMC-integrated system has five operation modes and three common characteristics under the duration of the fault. The study also reveals several instances of RS performance degradation such as AC voltage loop saturation, and shows that RS power reversal can be significantly improved. An enhanced AC FRT control method is proposed to achieve controllable PCC voltage and continuous power transmission by actively reducing the PCC voltage amplitude. The robustness of the method is theoretically proven under parameter variation and operation mode switching. Finally, the feasibility of the proposed method is verified through MAT-LAB/Simulink results.
引用
收藏
页码:1316 / 1330
页数:15
相关论文
共 28 条
[21]   A fault ride-through control strategy for DFIG-based wind farm with VSC-HVDC grid-integration [J].
Liao, Yong ;
Wang, Guodong .
Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2014, 38 (23) :13-21and39
[22]   Enhanced Fault Ride - Through Ability of DFIG-Based Wind Energy System Using Superconducting Fault Current Limiter [J].
Sahoo, Subhendu Sekhar ;
Mishra, Anirban ;
Chatterjee, Kalyan ;
Sharma, Chandan Kumar .
2017 4TH INTERNATIONAL CONFERENCE ON POWER, CONTROL & EMBEDDED SYSTEMS (ICPCES), 2017,
[23]   Rethinking Fault Ride-Through Control of DFIG-Based Wind Turbines From New Perspective of Rotor-Port Impedance Characteristics [J].
Zhu, Donghai ;
Wang, Zhen ;
Hu, Jiabing ;
Zou, Xudong ;
Kang, Yong ;
Guerrero, Josep M. .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2024, 15 (03) :2050-2062
[24]   Improved fault ride through capability of DFIG based wind turbines using synchronous reference frame control based dynamic voltage restorer [J].
Jerin, A. Rini Ann ;
Kaliannan, Palanisamy ;
Subramaniam, Umashankar .
ISA TRANSACTIONS, 2017, 70 :465-474
[25]   A Modified DC Chopper for Limiting the Fault Current and Controlling the DC-Link Voltage to Enhance Fault Ride-Through Capability of Doubly-Fed Induction-Generator-Based Wind Turbine [J].
Naderi, Seyed Behzad ;
Negnevitsky, Michael ;
Muttaqi, Kashem M. .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2019, 55 (02) :2021-2032
[26]   A Fuzzy Based Improved Control Strategy of Dynamic Voltage Restorer for Low Voltage and High Voltage Ride Through Compensation for Variable Speed Hybrid Energy System [J].
R. Uthra ;
D. Suchitra .
Wireless Personal Communications, 2022, 127 (3) :2391-2415
[27]   A Fuzzy Based Improved Control Strategy of Dynamic Voltage Restorer for Low Voltage and High Voltage Ride Through Compensation for Variable Speed Hybrid Energy System [J].
Uthra, R. ;
Suchitra, D. .
WIRELESS PERSONAL COMMUNICATIONS, 2022, 127 (03) :2391-2415
[28]   Improved Fault Ride Through Capability in DFIG Based Wind Turbines Using Dynamic Voltage Restorer With Combined Feed-Forward and Feed-Back Control [J].
Amalorpavaraj, Rini Ann Jerin ;
Kaliannan, Palanisamy ;
Padmanaban, Sanjeevikumar ;
Subramaniam, Umashankar ;
Ramachandaramurthy, Vigna K. .
IEEE ACCESS, 2017, 5 :20494-20503