A Measurement Method for the Charging Potential of Conductors in the Vicinity of HVDC Overhead Lines Based on a Non-Contact Electrometer

被引:0
作者
Shi, Jinpeng [1 ]
Guo, Xingxin [2 ]
Wang, Donglai [1 ,3 ]
Chen, Bo [3 ,4 ]
Zhao, Yan [1 ]
Zhang, Aijun [1 ]
机构
[1] Shenyang Inst Engn, Key Lab Reg Multienergy Syst Integrat & Control Li, Shenyang 110136, Peoples R China
[2] State Grid Jiangsu Elect Power Co Ltd, Res Inst, Nanjing 211103, Peoples R China
[3] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewable, Beijing 102206, Peoples R China
[4] China Elect Power Res Inst, Beijing 100192, Peoples R China
关键词
charging potential; electrostatic field; HVDC overhead line; non-contact measurement; ION FLOW-FIELD; ELECTRIC-FIELD; VOLTAGE; MODEL; MILL;
D O I
10.3390/electronics12224567
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Charging potential appears when a conductor insulated to the ground is exposed to an electrostatic field. A modified measurement method based on a non-contact electrometer is presented in this article. This system is appropriate for measuring the charging potential of a conductor near high-voltage direct-current (HVDC) overhead lines. Compared with the contact measurement method, the modified method is hardly affected by the internal resistance of the electrometer, which helps ensure measurement accuracy in the electrostatic field. In contrast with the traditional non-contact electrometer, the electric field generated by HVDC lines and the space charges around the electrometer probe are shielded using a grounding cage. The effectiveness of the modified measurement method was verified via experiments. The impacts of the structure and position of the measurement system on the measured charging potential are discussed.
引用
收藏
页数:12
相关论文
共 23 条
  • [1] The influence of greenhouse support structures on ion flow field under overhead high voltage direct current lines
    Chen, Bo
    Lu, Tiebing
    Bai, Bin
    Shen, Nanxuan
    Zhang, Yuanhang
    Wang, Donglai
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2021, 196
  • [2] Cheng Q., 2020, IEEE T MAGN, V56, P1, DOI [10.1109/TMAG.2019.2955483, DOI 10.1109/TMAG.2019.2955483]
  • [3] Model, Design, and Testing of Field Mill Sensors for Measuring Electric Fields Under High-Voltage Direct-Current Power Lines
    Cui, Yong
    Yuan, Haiwen
    Song, Xiao
    Zhao, Luxing
    Liu, Yumeng
    Lin, Liwei
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2018, 65 (01) : 608 - 615
  • [4] Fu W., 2010, P DIGESTS 2010 14 BI
  • [5] Received signal strength indication-based localisation method with unknown path-loss exponent for HVDC electric field measurement
    Gu, Xiaolan
    Cui, Yong
    Wang, Qiusheng
    Yuan, Haiwen
    Zhao, Luxing
    Wu, Guifang
    [J]. HIGH VOLTAGE, 2017, 2 (04): : 261 - 266
  • [6] Measurements of Electrical Potential of Constant Charge Objects
    Kacprzyk, Ryszard
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (01) : 134 - 139
  • [7] Human-to-metal electrostatic discharge current measurements - Notes on the ESD current waveform
    Katsivelis, Pavlos S.
    Gonos, Ioannis F.
    Stathopulos, Ioannis A.
    [J]. JOURNAL OF ELECTROSTATICS, 2015, 77 : 182 - 190
  • [8] Electrostatic behaviour of wood and laminate floor coverings and current situation in standardisation
    Kleber, Detlef
    [J]. JOURNAL OF ELECTROSTATICS, 2017, 88 : 218 - 224
  • [9] The finite element modeling of conductors and floating potentials
    Konrad, A
    Graovac, R
    [J]. IEEE TRANSACTIONS ON MAGNETICS, 1996, 32 (05) : 4329 - 4331
  • [10] The Ionized Fields and the Ion Current on a Human Model Under ±800-kV HVDC Transmission Lines
    Li, Xuebao
    Cui, Xiang
    Zhen, Yongzan
    Lu, Tiebing
    Luo, Zhaonan
    Fang, Chao
    Zhou, Xiangxian
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (04) : 2141 - 2149