Fault Location Scheme for Multi-Terminal Transmission Line Based on Frequency-Dependent Traveling Wave Velocity and Distance Matrix

被引:7
作者
Zeng, Ruochen [1 ]
Zhang, Luliang [1 ]
Wu, Qing-Hua [1 ]
机构
[1] South China Univ Technol, Sch Elect Power Engn, Guangzhou 510641, Peoples R China
基金
中国国家自然科学基金;
关键词
Power transmission lines; Transmission line matrix methods; Fault location; Matrix decomposition; Dispersion; Transmission line measurements; Time-frequency analysis; Distance matrix; fault location; frequency-dependent traveling wave velocity; multi-terminal transmission line; PROTECTION; ALGORITHM;
D O I
10.1109/TPWRD.2023.3293998
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This article presents a novel traveling wave (TW) fault location scheme suitable for multi-terminal transmission line. Firstly, Successive Variational Mode Decomposition (SVMD) and Teager Energy Operator (TEO) are used for feature extraction, and the TW velocity and TW arrival time are obtained. Secondly, the fault section identification method is derived based on the perspective of frequency-dependent TW velocity instead of constant one, and the intrinsic distance matrix (IDM), fault distance matrix (FDM) and fault section identification matrix (FSIM) are defined. Thirdly, the fault section and reference terminal are identified by analyzing the characteristic of elements in FSIM. Finally, the estimated location is determined according to the average value of fault distances calculated on the paths containing the selected reference terminal and real fault point. Extensive simulation studies are conducted in PSCAD/EMTDC, and the test results demonstrated that the proposed method is feasible and reliable under various fault situations.
引用
收藏
页码:3980 / 3990
页数:11
相关论文