Evaluation of aging and degradation for silicone rubber composite insulator based on machine learning

被引:4
作者
Liu, Yushun [1 ]
Cheng, Yang [1 ]
Lv, Li [2 ]
Zeng, Xin [2 ,3 ]
Xia, Lingzhi [1 ]
Li, Senlin [1 ]
Liu, Jing [1 ]
Kong, Fei [2 ]
Shao, Tao [2 ,3 ]
机构
[1] State Grid Anhui Elect Power Res Inst, Hefei, Peoples R China
[2] Chinese Acad Sci, Inst Elect Engn, Beijing Int S&T Cooperat Base Plasma Sci & Energy, Beijing, Peoples R China
[3] Univ Chinese Acad Sci, Beijing, Peoples R China
基金
中国国家自然科学基金;
关键词
silicone rubber; composite insulator; aging degree; machine learning; decision tree; LIFE-SPAN PREDICTION; HIGH-TEMPERATURE; FLASHOVER; HYDROPHOBICITY; CONTAMINATION; DECAY;
D O I
10.1088/1361-6463/ace78c
中图分类号
O59 [应用物理学];
学科分类号
摘要
Silicone rubbers (SIRs), as the main material of composite insulator sheds, have aging phenomenon for the long-term operation in the outdoor, which has an important impact on the performance degradation of composite insulator. Periodic examine and replacement of severely aged composite insulator is of great significance for the safe operation of power system. However, there is no clear standard to estimate the aging degree. In order to evaluate the degree of aging and degradation more accurately, the experimental test and analysis of the SIR sheds were carried out from three aspects: physical characteristics, chemical composition and electrical properties. The physical characteristic results show that the surface of the aging SIR will appear obvious holes and cracks, as well as hardening. Chemical composition results show that the internal composition of the continuous decomposition, while a large number of heavy metal elements accumulate in the pollution. The change of physical characteristics and chemical composition of SIR sheds may lead to the deterioration of electrical properties. According to the above results, the influence rule of measurement parameters and aging degree was obtained, and the key characteristic parameters of aging were summarized and extracted. Based on the characteristic parameters, a decision tree aging evaluation model is established for state evaluation. The accuracy of machine learning is 100% and 93.2% respectively. For the on-site application, early warning of moderately aged insulators and replacement of severely aged insulators are proposed in the on-site maintenance of SIR composite insulators.
引用
收藏
页数:12
相关论文
共 57 条
  • [1] Aging of silicone rubber-based composite insulators under multi-stressed conditions: an overview
    Akbar, M.
    Ullah, R.
    Alam, S.
    [J]. MATERIALS RESEARCH EXPRESS, 2019, 6 (10)
  • [2] Amin M, 2007, SCI CHINA SER E, V50, P697, DOI 10.1007/s11431-007-0053-X
  • [3] Accelerated aging investigation of silicone rubber/silica composites for coating of high-voltage insulators
    Amin, Muhammad
    Khattak, Abraiz
    Ali, Muhammad
    [J]. ELECTRICAL ENGINEERING, 2018, 100 (01) : 217 - 230
  • [4] Amin M, 2014, REV ADV MATER SCI, V36, P29
  • [5] Study on Corona Aging Characteristics of Silicone Rubber Material Under Different Environmental Conditions
    Bi, Maoqiang
    Deng, Runkun
    Jiang, Tianyan
    Chen, Xi
    Pan, Aichuan
    Zhu, Lingzhi
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2022, 29 (02) : 534 - 542
  • [6] Wetting characteristics of artificial contamination on the hydrophobic surface
    Cao, Bin
    Wang, Liming
    [J]. ENGINEERING FAILURE ANALYSIS, 2019, 100 : 428 - 438
  • [7] Condition Assessment Strategies of Composite Insulator Based on Statistic Methods
    Chen, Can
    Jia, Zhidong
    Ye, Wei'an
    Guan, Zhicheng
    Li, Yaozhong
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (06) : 3231 - 3241
  • [8] Aging Characterization and Lifespan Prediction of Silicone Rubber Material Utilized for Composite Insulators in Areas of Atypical Warmth and Humidity
    Cheng, L.
    Wang, L.
    Guan, Z.
    Zhang, F.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (06) : 3547 - 3555
  • [9] Research on Aging Evaluation and Remaining Lifespan Prediction of Composite Insulators in High Temperature and Humidity Regions
    Cheng, L.
    Mei, H.
    Wang, L.
    Guan, Z.
    Zhang, F.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (05) : 2850 - 2857
  • [10] Research on the long-time operation performance of composite insulator shed hydrophobicity under hydrothermal conditions
    Cheng, Li
    Shao, Shanfeng
    Zhang, Sida
    Liao, Ruijin
    Yang, Lijun
    Guo, Chenjun
    [J]. HIGH VOLTAGE, 2018, 3 (01): : 67 - 72