Experimental studies on natural bank type heating/cooling energy saving Air conditioning system

被引:1
作者
Goyal, Vaishali [1 ]
Asati, Arun Kumar [1 ]
Garg, Rajeev Kumar [2 ]
Arora, Amit [2 ]
机构
[1] Shaheed Bhagat Singh State Univ, Dept Mech Engn, Ferozepur, Punjab, India
[2] Shaheed Bhagat Singh State Univ, Dept Chem Engn, Ferozepur, Punjab, India
关键词
Earth air heat exchanger; full factorial design; factor interactions; effectiveness; temperature difference; dry bulb temperature; wet bulb temperature; earth's undisturbed temperature; EARTH-TO-AIR; HEAT-EXCHANGER; PERFORMANCE; VENTILATION; SIMULATION; BUILDINGS; SUMMER; HOT;
D O I
10.1177/09544089221096052
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
The present study reports air-based novel energy saving compact bank type earth air heat exchanger system (EAHE) (having only 25m(2) area) fabricated from Polyvinylchloride pipes of nominal diameter 0.203 mm (8 inches) for inlet and outlet headers and main pipes and 0.150 mm (6 inches nominal diameter) for branched pipes, which is installed in Shaheed Bhagat Singh State University, Ferozepur in Punjab state, India (North West border area of India) and studied for the duration from April to August 2021 using the full factorial design with four inlet variables at multilevel to find a model equation between inlet and outlet variables, i.e., heat exchanger effectiveness and achieved temperature difference. An induced airflow mode has been used to provide near-uniform flow through all corresponding pipes of symmetrical-shaped earth air heat exchangers. The values of Dry bulb temperature (DBT) and wet bulb temperature (WBT) have been measured for air inlet, for air outlet, as well as for ambient air using resistance temperature detectors (RTD) installed at the requisite locations. Earth's undisturbed temperature (EUT) was also noted by installing RTD at a depth of 2 m, and the average measured value of EUT is found to be 28.5 degrees C. The current system has imparted the temperature difference variation from 0.4 C-o to 9.4 C-o, and the effectiveness varied from 0.16 to 0.82 during the whole season. This system could give a cooling potential of 0.0523 kJ/s to 1.587 kJ/s using a mass flow rate of 0.163 kg/s.Experiments have been designed methodically to apply the full factorial technique. Most favorable parameters have been found for hot and dry and hot and humid weather. The current study is novel in terms of significantly improving the effectiveness of EAHE and addressing the central issue of space limitation in urban areas.
引用
收藏
页码:91 / 100
页数:10
相关论文
共 59 条
  • [21] Hamdane S., 2020, SCI ENG PROG, V21
  • [22] Further realistic annual simulations of earth-air heat exchangers installations in a coastal city
    Hermes, V. F.
    Ramalho, J. V. A.
    Rocha, L. A. O.
    dos Santos, E. D.
    Marques, W. C.
    Costi, J.
    Rodrigues, M. K.
    Isoldi, L. A.
    [J]. SUSTAINABLE ENERGY TECHNOLOGIES AND ASSESSMENTS, 2020, 37 (37)
  • [23] Islam, 2019, IMPLEMENTATION ECO F
  • [24] Ismael Hasan, 2018, J ENG SUSTAIN DEV, V22, P10
  • [25] Jamshidi N., 2020, PART RECOVER UTIL EN, V42, P3045
  • [26] Parameters optimization of a vertical ground heat exchanger based on response surface methodology
    Khalajzadeh, Vahid
    Heidarinejad, Ghassem
    Srebric, Jelena
    [J]. ENERGY AND BUILDINGS, 2011, 43 (06) : 1288 - 1294
  • [27] Computer simulation of ground-coupled liquid desiccant air conditioner for sub-tropical regions
    Lee, C. K.
    Lam, H. N.
    [J]. INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2009, 48 (12) : 2365 - 2374
  • [28] Lekhal, 2020, MATEC WEB C, V307
  • [29] Effect of geo-climatic conditions and pipe material on heating performance of earth-air heat exchangers
    Lekhal, Mohammed Cherif
    Benzaama, Mohammed-Hichem
    Kindinis, Andrea
    Mokhtari, Abderahmane-Mejedoub
    Belarbi, Rafik
    [J]. RENEWABLE ENERGY, 2021, 163 : 22 - 40
  • [30] Application of ground-heat-source water thermal-storage with a heat-pump cooling and heating system
    Lim, K. B.
    Lee, S. H.
    Lee, C. H.
    [J]. PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART E-JOURNAL OF PROCESS MECHANICAL ENGINEERING, 2010, 224 (E1) : 73 - 78