Experimental studies on natural bank type heating/cooling energy saving Air conditioning system

被引:1
作者
Goyal, Vaishali [1 ]
Asati, Arun Kumar [1 ]
Garg, Rajeev Kumar [2 ]
Arora, Amit [2 ]
机构
[1] Shaheed Bhagat Singh State Univ, Dept Mech Engn, Ferozepur, Punjab, India
[2] Shaheed Bhagat Singh State Univ, Dept Chem Engn, Ferozepur, Punjab, India
关键词
Earth air heat exchanger; full factorial design; factor interactions; effectiveness; temperature difference; dry bulb temperature; wet bulb temperature; earth's undisturbed temperature; EARTH-TO-AIR; HEAT-EXCHANGER; PERFORMANCE; VENTILATION; SIMULATION; BUILDINGS; SUMMER; HOT;
D O I
10.1177/09544089221096052
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
The present study reports air-based novel energy saving compact bank type earth air heat exchanger system (EAHE) (having only 25m(2) area) fabricated from Polyvinylchloride pipes of nominal diameter 0.203 mm (8 inches) for inlet and outlet headers and main pipes and 0.150 mm (6 inches nominal diameter) for branched pipes, which is installed in Shaheed Bhagat Singh State University, Ferozepur in Punjab state, India (North West border area of India) and studied for the duration from April to August 2021 using the full factorial design with four inlet variables at multilevel to find a model equation between inlet and outlet variables, i.e., heat exchanger effectiveness and achieved temperature difference. An induced airflow mode has been used to provide near-uniform flow through all corresponding pipes of symmetrical-shaped earth air heat exchangers. The values of Dry bulb temperature (DBT) and wet bulb temperature (WBT) have been measured for air inlet, for air outlet, as well as for ambient air using resistance temperature detectors (RTD) installed at the requisite locations. Earth's undisturbed temperature (EUT) was also noted by installing RTD at a depth of 2 m, and the average measured value of EUT is found to be 28.5 degrees C. The current system has imparted the temperature difference variation from 0.4 C-o to 9.4 C-o, and the effectiveness varied from 0.16 to 0.82 during the whole season. This system could give a cooling potential of 0.0523 kJ/s to 1.587 kJ/s using a mass flow rate of 0.163 kg/s.Experiments have been designed methodically to apply the full factorial technique. Most favorable parameters have been found for hot and dry and hot and humid weather. The current study is novel in terms of significantly improving the effectiveness of EAHE and addressing the central issue of space limitation in urban areas.
引用
收藏
页码:91 / 100
页数:10
相关论文
共 59 条
[1]  
Agostino DD., 2016, INT J HEAT TECHNOL, V34
[2]  
Alkhalaf Haitham, 2018, Journal of Clean Energy Technologies, V6, P106, DOI 10.18178/jocet.2018.6.2.443
[3]   Influence of geometrical parameters on the flow characteristics of multi-pipe earth-to-air heat exchangers -experimental and CFD investigations [J].
Amanowicz, Lukasz .
APPLIED ENERGY, 2018, 226 :849-861
[4]   Experimental investigation and CFD simulation of multi-pipe earth-to-air heat exchangers (EAHEs) flow performance [J].
Amanowicz, Lukasz ;
Wojtkowiak, Janusz .
INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY SYSTEMS AND ENVIRONMENTAL ENGINEERING (ASEE17), 2017, 22
[5]   Design of a Ventilation System Coupled with a Horizontal Air-Ground Heat Exchanger (HAGHE) for a Residential Building in a Warm Climate [J].
Baglivo, Cristina ;
D'Agostino, Delia ;
Congedo, Paolo Maria .
ENERGIES, 2018, 11 (08)
[6]  
Baniyounes AM., 2020, INT J ELECTR COMPUT, V10, P3948
[7]   Numerical and experimental investigation on the transient behavior of an earth air heat exchanger in continuous operation mode [J].
Belloufi, Yousef ;
Brima, Abdelhafid ;
Zerouali, Sakina ;
Atmani, Rachid ;
Aissaoui, Faris ;
Rouag, Amar ;
Moummi, Noureddine .
International Journal of Heat and Technology, 2017, 35 (02) :279-288
[8]   Contribution to the Study of the Reduction of Energy Consumption through the Exchanger Coupled Conventional Air-Ground-Air Conditioner. Application to the Building [J].
Benhamza, Mohamed E. ;
Brima, Abdelhafid ;
Houda, Saddok ;
Moummi, Noureddine .
Heat Transfer - Asian Research, 2017, 46 (08) :1104-1118
[9]   An experimental and a numerical study of horizontal earth-air heat exchanger in a hot climate [J].
Benhamza, Mohamed El Ghazali ;
Brima, Abdelhafid ;
Houda, Saddok ;
Moummi, Noureddine .
International Journal of Sustainable Engineering, 2017, 10 (02) :82-89
[10]   European project "Cheap-GSHPs": installation and monitoring of newly designed helicoidal ground source heat exchanger on the German test site [J].
Bertermann, David ;
Bernardi, Adriana ;
Pockele, Luc ;
Galgaro, Antonio ;
Cultrera, Matteo ;
de Carli, Michele ;
Mueller, Johannes .
ENVIRONMENTAL EARTH SCIENCES, 2018, 77 (05)