Optimal Planning of Urban Building-Type Integrated Energy Systems Considering Indoor Somatosensory Comfort and PV Consumption

被引:1
作者
You, Guangzeng [1 ]
Sun, Peng [1 ]
Lei, Yi [2 ]
Zhang, Donghui [2 ]
Li, Haibo [2 ]
机构
[1] Yunnan Power Grid Co Ltd, Power Grid Planning & Construction Res Ctr, Kunming 130022, Peoples R China
[2] Tsinghua Univ, Sichuan Energy Internet Res Inst, Chengdu 610213, Peoples R China
关键词
integrated energy systems (IES); buildings; optimization; indoor somatosensory comfort; PV consumption;
D O I
10.3390/su16010411
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Building energy consumption is the main urban energy consumption component, which mainly serves people-centered work and living energy demands. Based on the physical requirements of humans in urban buildings and to determine the comfortable body temperature in each season, this paper establishes a sizing optimization model of building-type integrated energy systems (IES) for sustainable development, where the cooling and heating loads required to maintain indoor somatosensory body comfort temperature are calculated. Depending on the external energy price, internal power balance, and other constraints, the model develops an optimal sizing and capacity-planning method of energy conversion and storage unit in a building-type IES with PV generation. The operating principle is described as follows: the PV generation is fully consumed, a gas engine satisfies the electric and thermal base load requirements, and the power system and a heat pump supply the remaining loads. The gas price, peak-valley electricity price gap, and heat-to-power ratio of gas engines are considered important factors for the overall techno-economic analysis. The developed method is applied to optimize the economic performance of building-type IES and verified by practical examples. The results show that using the complementary characteristics of different energy conversion units is important to the overall IES cost. A 300 kW building photovoltaic system can reduce the gas engine capacity from 936.7 kW to 854.7 kW, and the annual cost can be approximately reduced from 7.82 million to 7.50 million RMB yuan.
引用
收藏
页数:20
相关论文
共 19 条
[1]   A mixed integer programming model for optimal design of trigeneration in a hospital complex [J].
Arcuri, P. ;
Florio, G. ;
Fragiacomo, P. .
ENERGY, 2007, 32 (08) :1430-1447
[2]  
Cesena E., 2016, IEEE Trans. Smart Grid, V3, P48
[3]   Research on economic dispatch of integrated energy system based on improved krill swarm algorithm [J].
Deng, Zhi-guang ;
Yang, Jing-hua ;
Dong, Chen-long ;
Xiang, Mei-qiong ;
Qin, Yue ;
Sun, Yong-sheng .
ENERGY REPORTS, 2022, 8 :77-86
[4]   Heat-electricity joint bidding strategies for intelligent buildings in intelligent building cluster [J].
Dou, Xun ;
Shao, Yunfan ;
Wang, Jun ;
Hu, Qinran .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 129
[5]  
Fanger P. O., 1970, Thermal comfort. Analysis and applications in environmental engineering.
[6]   The effect of correlation of uncertainties on collaborative optimization of integrated energy system [J].
Fu, Yu ;
Sun, Qie ;
Wennersten, Ronald .
ENERGY REPORTS, 2021, 7 :586-592
[7]   An Optimal Dispatch Algorithm for Managing Residential Distributed Energy Resources [J].
Karami, Hossein ;
Sanjari, Mohammad Javad ;
Hosseinian, Seyed Hossein ;
Gharehpetian, G. B. .
IEEE TRANSACTIONS ON SMART GRID, 2014, 5 (05) :2360-2367
[8]   Review on viability and implementation of residential PV-battery systems: Considering the case of Dominican Republic [J].
Lara, Edwin Garabitos ;
Garcia, Felix Santos .
ENERGY REPORTS, 2021, 7 :8868-8899
[9]  
Li W., 2013, Renewable Energy Resour., V31, P123
[10]   An autonomous hierarchical control for improving indoor comfort and energy efficiency of a direct expansion air conditioning system [J].
Mei, Jun ;
Xia, Xiaohua ;
Song, Mengjie .
APPLIED ENERGY, 2018, 221 :450-463