Sag Measurement Method of Wind-Induced Vibration for Uniced Overhead Power Line via Laser Rangefinder and Angle Monitoring

被引:2
作者
Zhang, Yuegang [1 ]
Fang, Yu [1 ]
Zhou, Xiaofa [2 ]
Liu, Xintian [1 ]
Yang, Hao [1 ]
Xu, Yang [2 ]
Wu, Xin [1 ]
Ren, Xingzhi [1 ]
机构
[1] Shanghai Univ Engn Sci, Sch Mech & Automot Engn, Shanghai 201620, Peoples R China
[2] State Grid Shanghai Municipal Elect Power Co, Shanghai 200122, Peoples R China
关键词
Angle monitoring; laser rangefinder; overhead power line; sag measurement; wind-induced vibration; VORTEX FLOWMETER; KALMAN FILTER; TRACKING;
D O I
10.1109/TIM.2023.3334362
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The sag of overhead power lines is an important indicator of the construction quality and safe operation of power lines. If the sag is too large or too small, it will threaten the safety of the lines and lead to serious power grid accidents. Existing sag measurement methods have problems such as high manual labor intensity, complex deployment, and high operational requirements. This article considers the influence of wind-induced vibration, establishes a wind-induced vibration model and measurement model, and proposes a sag measurement method that combines laser ranging and angle sensors. The proposed method can be applied to actual engineering scenarios such as daily maintenance of power line sag, on-site construction, and small-scale monitoring. When the laser is perpendicular to the wire, the horizontal angle theta(vertical) recorded by the angle sensor is an important parameter for calculating the 3-D coordinate data. In this work, a nonparametric estimation method is introduced for the first time to calculate the angle. In the 2-D plane, the improved progressive sample consensus (PROSAC) algorithm and the adaptive random sample consensus (RANSAC) algorithm are used to double filter the error points in the measurement data under the influence of wind-induced vibration, a 3-D model of the power line is fit, and the stochastic gradient descent (SGD) method is used to find the lowest point of sag and finally calculate the tangent sag. Experiments have proven that the calculation accuracy of the method in this work meets the requirements of the industry. It has the characteristics of convenient deployment, safety, and stability, which improves the safety and efficiency of overhead power line sag measurement work.
引用
收藏
页码:1 / 16
页数:16
相关论文
共 21 条
[1]  
Akresh M., 2010, 2010 IEEE International Instrumentation & Measurement Technology Conference - I2MTC 2010, P234, DOI 10.1109/IMTC.2010.5488084
[2]  
[Anonymous], 1995, Guide to the expression of uncertainty in measurement, V2
[3]  
[Anonymous], 2012, Introduction: Adversarial Relations? Business
[4]   Vortex signal model based Kalman filter of vortex signal processing method [J].
Chen, Jie ;
Hou, Zhen-Yu ;
Li, Bin ;
Wang, Si-Cheng .
REVIEW OF SCIENTIFIC INSTRUMENTS, 2022, 93 (04)
[5]   Novel algorithm of tracking band-pass digital filter with amplitude 1/f2 attenuation for vortex signal extraction [J].
Chen, Jie ;
Fan, Chenyang ;
Li, Bin ;
Yin, Jian ;
Liu, Xiaojia .
FLOW MEASUREMENT AND INSTRUMENTATION, 2015, 45 :82-92
[6]   A Phase Difference Measurement Method Based on the Extended Kalman Filter for Coriolis Mass Flowmeters [J].
Chen, Nan ;
Fan, Shangchun ;
Zheng, Dezhi .
MEASUREMENT SCIENCE REVIEW, 2019, 19 (02) :48-52
[7]   A dual phase-locked loop for vortex flow metering [J].
Clarke, DW ;
Ghaoud, T .
FLOW MEASUREMENT AND INSTRUMENTATION, 2003, 14 (1-2) :1-11
[8]  
Ding H., 2019, P IEEE INT INSTR MEA, P1
[9]   Modelling and tracking a vortex flow-meter signal [J].
Ghaoud, T ;
Clarke, DW .
FLOW MEASUREMENT AND INSTRUMENTATION, 2002, 13 (03) :103-117
[10]   Anti-strong pipeline vibration method combining frequency variance and amplitude feature for vortex flowmeter [J].
Jiang, Zhen ;
Li, Ao ;
Xu, Ke-Jun ;
Xiong, Wei .
MEASUREMENT, 2020, 166