Multi-objective optimization of hollow fiber membrane-based water cooler for enhanced cooling performance and energy efficiency

被引:3
作者
Yan, Weichao [1 ]
Cui, Xin [1 ]
Meng, Xiangzhao [1 ]
Yang, Chuanjun [1 ]
Zhang, Yu [1 ]
Liu, Yilin [1 ]
An, Hui [2 ]
Jin, Liwen [1 ]
机构
[1] Xi An Jiao Tong Univ, Inst Bldg Environm & Sustainable Technol, Sch Human Settlements & Civil Engn, Xian 710049, Shaanxi, Peoples R China
[2] Singapore Inst Technol, Engn Cluster, 10 Dover Dr, Singapore 138683, Singapore
基金
中国国家自然科学基金;
关键词
Water-mediated evaporative cooling; Hollow fiber membrane; Multi-objective optimization; Response surface methodology; Genetic algorithm; DESICCANT AIR DEHUMIDIFICATION; MASS-TRANSFER; HEAT; FLOW; STRATEGY; SYSTEM; MODULE;
D O I
10.1016/j.renene.2023.119892
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Water-mediated evaporative cooling systems often suffer from cross-contamination, droplet carryover, and high maintenance costs. This study proposes a novel liquid cooling solution, the hollow fiber membrane-based water cooler (HFMWC), to address these issues. The primary innovation of this study lies in the optimization of key design parameters of the countercurrent HFMWC, aligning them with stringent engineering requirements. Two standard working conditions for wet cooling towers are considered. Numerical modeling and response surface methodology are used to develop regression models correlating six key parameters (water velocity, air/water ratio, fiber length, fiber inner diameter, membrane thickness, and packing fraction) with two performance evaluation indexes (outlet water temperature and consumptive electric power ratio). A genetic algorithm-based multi-objective optimization is employed to obtain Pareto fronts, representing optimal trade-offs between the two indexes. Using the ideal point method, relative optimal solutions are identified, resulting in water temperature drops of 7.56 degrees C and 13.07 degrees C, with consumptive electric power ratios of 0.0128 kW h/m3 and 0.0138 kW h/m3 for conditions I and II, respectively. Most solutions achieve the highest energy efficiency rating while satisfying the design temperature difference. The average deviations between optimized and simulated data for the two indexes are 0.88 % and 3.88 %, demonstrating the reliability of the derived optimal solutions for engineering design. These findings not only offer a promising way to overcome the limitations of traditional evaporative cooling systems, but also contribute to the broader field of sustainable and efficient thermal management technologies.
引用
收藏
页数:14
相关论文
共 54 条
[1]   State-of-the-art in liquid-to-air membrane energy exchangers (LAMEEs): A comprehensive review [J].
Abdel-Salam, Mohamed R. H. ;
Ge, Gaoming ;
Fauchoux, Melanie ;
Besant, Robert W. ;
Simonson, Carey J. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2014, 39 :700-728
[2]   Technological development of evaporative cooling systems and its integration with air dehumidification processes: A review [J].
Abdullah, Shekh ;
Zubir, Mohd Nashrul Bin Mohd ;
Bin Muhamad, Mohd Ridha ;
Newaz, Kazi Md Salim ;
Oztop, Hakan F. ;
Alam, Md Shadab ;
Shaikh, Kaleemullah .
ENERGY AND BUILDINGS, 2023, 283
[3]  
[Anonymous], 2018, GB/T, 1-2018
[4]   Response surface methodology (RSM) based multi-objective optimization of fusel oil-gasoline blends at different water content in SI engine [J].
Awad, Omar I. ;
Mamat, R. ;
Ali, Obed M. ;
Azmi, W. H. ;
Kadirgama, K. ;
Yusri, I. M. ;
Leman, A. M. ;
Yusaf, T. .
ENERGY CONVERSION AND MANAGEMENT, 2017, 150 :222-241
[5]  
Chakraborty S., 2022, DECISION ANALYTICS J, V2, P100021, DOI [10.1016/j.dajour.2021.100021, DOI 10.1016/J.DAJOUR.2021.100021]
[6]   A novel evaporative cooling system with a polymer hollow fibre spindle [J].
Chen, Xiangjie ;
Su, Yuehong ;
Aydin, Devrim ;
Ding, Yate ;
Zhang, Shihao ;
Reay, David ;
Riffat, Saffa .
APPLIED THERMAL ENGINEERING, 2018, 132 :665-675
[7]   Recent research developments in polymer heat exchangers - A review [J].
Chen, Xiangjie ;
Su, Yuehong ;
Reay, David ;
Riffat, Saffa .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 60 :1367-1386
[8]   Study on optimization of indirect-direct evaporative chiller for producing cold water in hot and dry areas [J].
Chu, Junjie ;
Xu, Wei ;
Huang, Xiang ;
Geng, Zhichao ;
Xuan, Jingwen .
RENEWABLE ENERGY, 2022, 181 :898-913
[9]   Parametric study of a membrane-based semi-direct evaporative cooling system [J].
Cui, Xin ;
Yan, Weichao ;
Chen, Xiangjie ;
Wan, Yangda ;
Chua, Kian Jon .
ENERGY AND BUILDINGS, 2020, 228
[10]   Performance analysis of a hollow fiber membrane-based heat and mass exchanger for evaporative cooling [J].
Cui, Xin ;
Yan, Weichao ;
Liu, Yilin ;
Zhao, Min ;
Jin, Liwen .
APPLIED ENERGY, 2020, 271