Influence of three different pitches fillings on the cooling performance of wet cooling towers under crosswind

被引:15
作者
Yang, Jichong [1 ]
Jia, Zhenguo [2 ]
Guan, Hongjun [2 ]
He, Suoying [1 ]
Gao, Ming [1 ]
机构
[1] Shandong Univ, Sch Energy & Power Engn, Shandong Engn Lab High Efficiency Energy Conservat, Jinan 250061, Shandong, Peoples R China
[2] Shengli Power Plant, Dongying 257087, Shandong, Peoples R China
关键词
Wet cooling tower; Crosswind; Three different pitches fillings; Cooling performance; Numerical simulation; THERMAL PERFORMANCE; OPTIMIZATION; ENHANCEMENT; SIMULATION;
D O I
10.1016/j.applthermaleng.2022.119760
中图分类号
O414.1 [热力学];
学科分类号
摘要
For a super-large wet cooling tower, the three-dimensional numerical model is established and verified for three different pitches fillings consisting of 20 mm S-wave, 26 mm S-wave and 30 mm oblique folded wave fillings. The research obtains the relatively optimal fillings layout with three different pitches and analyzes the influence of three different pitches fillings on the performance of the wet cooling tower under windless and crosswind. The findings show that three different pitches fillings can improve the distribution of air dynamic and temperature fields inside the tower. For the wind speed of v = 5 m/s, the inner zone radius (R ' 1) of 37.5 m and the middle ring width (R ' 2) of 10 m is the relatively optimal fillings layout with three different pitches, in which the water temperature drop and cooling efficiency are 10.5 degrees C and 60.91%, respectively. Compared with 20 mm uniform fillings, the water temperature drop, cooling efficiency, ventilation and evaporation loss increase by about 0.20 degrees C, 1.1%, 552 kg/s and 8.9 kg/s, respectively. Additionally, the relatively optimal fillings with three different pitches can significantly increase the cooling capacity of the wet cooling tower under windless and wind speeds v = 1-6 m/s.
引用
收藏
页数:13
相关论文
共 50 条
  • [31] Thermal performance analysis for high level water collecting wet cooling tower under crosswind conditions
    Gao, Ming
    Zou, Jian
    He, Suoying
    Sun, Fengzhong
    [J]. APPLIED THERMAL ENGINEERING, 2018, 136 : 568 - 575
  • [32] Theoretical Prediction With Numerical and Experimental Verification to Predict Crosswind Effects on the Performance of Cooling Towers
    Hooman, Kamel
    [J]. HEAT TRANSFER ENGINEERING, 2015, 36 (05) : 480 - 487
  • [33] Effect mechanism of air deflectors on the cooling performance of dry cooling tower with vertical delta radiators under crosswind
    Zhao, Yuanbin
    Long, Guoqing
    Sun, Fengzhong
    Li, Yan
    Zhang, Cuijiao
    Liu, Jiabin
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2015, 93 : 321 - 331
  • [34] The Lewis factor and its influence on the performance prediction of wet-cooling towers
    Kloppers, JC
    Kröger, DG
    [J]. INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2005, 44 (09) : 879 - 884
  • [35] A sensitivity-coefficients method for predicting thermal performance of natural draft wet cooling towers under crosswinds
    Chen, Kun
    Sun, Fengzhong
    Zhang, Lei
    Chen, Xuehong
    Zhang, Xiaoyu
    [J]. APPLIED THERMAL ENGINEERING, 2022, 206
  • [36] Comparison on the cooling performance of mechanical draft dry cooling towers pre-cooled with nozzle spray and wet medium
    Zhao, Cuilin
    Wang, Mingwei
    Gao, Qi
    Cheng, Shen
    Liu, Zhilan
    Geng, Zhe
    Zhang, Shuzhen
    He, Suoying
    Qi, Jianhui
    Han, Kuihua
    Gao, Ming
    Shi, Yuetao
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2023, 156 : 298 - 314
  • [37] Numerical simulation on influence of noise barrier on thermal performance for natural draft wet cooling towers
    Zheng, Zhirui
    Zhang, Deying
    Jiang, Lei
    Zhang, Zhengqing
    He, Suoying
    Gao, Ming
    [J]. CASE STUDIES IN THERMAL ENGINEERING, 2021, 28
  • [38] Effects of ZnO/water nanofluid on the thermal performance of wet cooling towers
    Rahmati, Mehdi
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 131 : 526 - 534
  • [39] Windbreak walls reverse the negative effect of crosswind in short natural draft dry cooling towers into a performance enhancement
    Lu, Y.
    Guan, Z.
    Gurgenci, H.
    Zou, Z.
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2013, 63 : 162 - 170
  • [40] A review of the crosswind effect on the natural draft cooling towers
    Li, Xiaoxiao
    Gurgenci, Hal
    Guan, Zhiqiang
    Wang, Xurong
    Xia, Lin
    [J]. APPLIED THERMAL ENGINEERING, 2019, 150 : 250 - 270