Data-driven fault location approach in AC/DC microgrids based on fault voltage and current differences

被引:5
作者
Daisy, Mohammad [1 ]
Aliabadi, Mahmood Hosseini [1 ]
Javadi, Shahram [1 ,2 ]
Naimi, Hasan Meyar [1 ]
机构
[1] Islamic Azad Univ, Dept Elect Engn, Cent Tehran Branch, Tehran, Iran
[2] Islamic Azad Univ, Intelligent Power Syst Res Ctr, Cent Tehran Branch, Tehran, Iran
关键词
Fault Location; Hybrid Microgrid; Fault Current and Voltage Difference; Renewable Sources; DISTRIBUTION NETWORK;
D O I
10.1016/j.segan.2023.101235
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In recent years, various fault location techniques for microgrids have been presented. Some of these methods estimate the distance or section of the fault by assuming the availability of data from all measuring nodes, which is not economically viable. Moreover, the accuracy of these techniques is sensitive to the type of sources, fault location, resistance, inception angle, and they require accurate line models and enormous data banks. The prominent disadvantage of these methods is their performance for DC or AC networks separately. This article suggests a method to estimate both the distance of the fault and faulty section in a hybrid microgrid (DC/AC) using the pi line model. This method begins by analyzing the voltages and currents of all buses based on the data collected at the points of common coupling and DG locations. Then, by analyzing the voltage and current difference at the buses of each branch, the fault location is determined. The proposed approach does not require DG models and needs a quarter of the data cycle. A 15-node hybrid microgrid is implemented in MATLAB, and a 7node AC microgrid is implemented in the power systems simulator to evaluate the suggested technique. The results confirm the insensitivity of this approach to the different fault types, locations, inception angles, inductances, high impedance fault (500 ohm), DG operating conditions, and line parameters. In addition, the proposed algorithm is investigated by considering the measurement error. The results show the suitable accuracy of this scheme compared to other similar methods.
引用
收藏
页数:20
相关论文
共 50 条
[21]   Fault detection and location in medium-voltage DC microgrids using travelling-wave reflections [J].
Saleh, Khaled ;
Hooshyar, Ali ;
El-Saadany, Ehab F. .
IET RENEWABLE POWER GENERATION, 2020, 14 (04) :571-579
[22]   Fault location of a small current grounding fault based on distribution characteristics of zero sequence voltage [J].
Liu J. ;
Dong L. ;
Xue C. ;
Xue Y. ;
Li J. ;
Chen Y. .
Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2022, 50 (03) :59-67
[23]   Data-Driven Fault Location of Electric Power Distribution Systems With Distributed Generation [J].
Jiang, Yazhou .
IEEE TRANSACTIONS ON SMART GRID, 2020, 11 (01) :129-137
[24]   A Sparse-Data-Driven Approach for Fault Location in Transmission Networks [J].
Majidi, Mehrdad ;
Etezadi-Amoli, Mehdi ;
Fadali, Mohammed Sami .
IEEE TRANSACTIONS ON SMART GRID, 2017, 8 (02) :548-556
[25]   Fault Location Estimation in Voltage-Source-Converter-Based DC System: The L Location [J].
Li, Dongyu ;
Ukil, Abhisek .
AMERICAN JOURNAL OF CLINICAL NUTRITION, 2021, :11198-11209
[26]   Fault Location Estimation in Voltage-Source-Converter-Based DC System: The L Location [J].
Li, Dongyu ;
Ukil, Abhisek .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2022, 69 (11) :11198-11209
[27]   Data-Driven Probabilistic Fault Location of Electric Power Distribution Systems Incorporating Data Uncertainties [J].
Jiang, Yazhou .
IEEE TRANSACTIONS ON SMART GRID, 2021, 12 (05) :4522-4534
[28]   Improvements to Fault Location Analysis Based on Voltage Sag Data - Verifying the Improvements to the Fault Location Accuracy of the Prototype Tool [J].
Shibata, Takeo ;
Fujita, Toshikazu ;
Yoshimura, Kenji ;
Nagashima, Hiroshi .
2008 IEEE 2ND INTERNATIONAL POWER AND ENERGY CONFERENCE: PECON, VOLS 1-3, 2008, :651-+
[29]   Accurate Fault Location in AC/DC Hybrid Line Corridors Based on Eigenvalue Decomposition [J].
Lu, Dayou ;
Liu, Yu ;
Huang, Wentao ;
Xi, Xinze .
2020 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2020,
[30]   Distributed Fault Location Based on Comprehensive Analysis of Fault Current [J].
Liu, Yadong ;
Sheng, Gehao ;
Shen, Xiaojun ;
Jiang, Xiuchen ;
Sun, Xuri ;
Wang, Shiqiang ;
Yang, Weiwei .
PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, :999-1002