Sliding mode control of four-leg inverters in a stand-alone microgrid for unbalance, neutral to ground voltage, and harmonics compensation

被引:0
|
作者
Ayoubi, Effat [1 ]
Miveh, Mohammad Reza [2 ]
Ghadimi, Ali Asghar [3 ]
Bagheri, Sajad [1 ]
Koushki, Masoud Mehrabi [3 ]
机构
[1] Islamic Azad Univ, Dept Elect Engn, Arak Branch, Arak, Iran
[2] Tafresh Univ, Dept Elect Engn, Tafresh, Iran
[3] Arak Univ, Fac Engn, Dept Elect Engn, Arak, Iran
关键词
neutral to ground voltage; sliding mode control; stand-alone microgrid; three-phase four-leg inverter; total harmonic distortion; unbalanced load condition; POWER QUALITY ENHANCEMENT; CONTROL STRATEGY; SYSTEMS; FILTER;
D O I
10.1049/rpg2.12804
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In a stand-alone microgrid, voltage control is an important issue to keep the grid balanced under unbalanced load conditions. The other important challenges in microgrids include handling the neutral to the ground voltage (NGV) as well as total harmonic distortion (THD) under its limits due to the IEEE standards. A four-leg inverter is the best choice for a three-phase transformerless inverter employed in a stand-alone microgrid. To control the inverter, sliding mode control (SMC) is a well-known nonlinear control system to handle unbalanced and nonlinear load conditions as it can provide high sinusoidal load voltage with high performance and fast dynamic response. This paper proposes an enhanced SMC control method for minimizing the NGV and THD in addition to compensating for unbalanced load voltage conditions simultaneously in a three-phase four-leg inverter. In order to verify the results of the proposed method, simulation results with MATLAB/Simulink are presented to confirm the effectiveness of the proposed SMC under various load conditions. The proposed method provided fast dynamic response and fixed switching frequency. Further, a significant reduction occurred in NGV and THD. The simulation results of this method compared with the MPC method indicated the better performance of the proposed method against the unbalanced and nonlinear various load conditions.
引用
收藏
页码:2964 / 2977
页数:14
相关论文
共 44 条
  • [1] A Model Predictive Control for a Four-Leg Inverter in a Stand-Alone Microgrid under Unbalanced Condition
    Koushki, Masoud Mehrabi
    Ayoubi, Effat
    Miveh, Mohammad Reza
    Ghadimi, Ali Asghar
    2021 12TH POWER ELECTRONICS, DRIVE SYSTEMS, AND TECHNOLOGIES CONFERENCE (PEDSTC), 2021, : 177 - 181
  • [2] Characteristic analysis of three-phase four-leg inverter based load unbalance compensator for stand-alone microgrid
    Kim, G. H.
    Hwang, C.
    Jeon, J. H.
    Byeon, G. S.
    Ahn, J. B.
    Jo, C. H.
    2015 9TH INTERNATIONAL CONFERENCE ON POWER ELECTRONICS AND ECCE ASIA (ICPE-ECCE ASIA), 2015, : 1491 - 1496
  • [3] A novel three-phase four-leg inverter based load unbalance compensator for stand-alone microgrid
    Kim, Gyeong-Hun
    Hwang, Chulsang
    Jeon, Jin-Hong
    Ahn, Jong-Bo
    Kim, Eung-Sang
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2015, 65 : 70 - 75
  • [4] Deadbeat Control of the Stand-Alone Four-Leg Inverter Considering the Effect of the Neutral Line Inductor
    Pichan, Mohammad
    Rastegar, Hasan
    Monfared, Mohammad
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2017, 64 (04) : 2592 - 2601
  • [5] Model-reference sliding mode control of a three-phase four-leg voltage source inverter for stand-alone distributed generation systems
    Ozdemir, Ayhan
    Yazici, Irfan
    Erdem, Zekiye
    TURKISH JOURNAL OF ELECTRICAL ENGINEERING AND COMPUTER SCIENCES, 2015, 23 (06) : 1817 - 1833
  • [6] Improved Voltage Unbalance and Harmonics Compensation Control Strategy for an Isolated Microgrid
    Moghaddam, Mohammad Jafar Hadidian
    Kalam, Akhtar
    Miveh, Mohammad Reza
    Naderipour, Amirreza
    Gandoman, Foad H.
    Ghadimi, Ali Asghar
    Abdul-Malek, Zulkurnain
    ENERGIES, 2018, 11 (10)
  • [7] Disturbance-Observer Assisted Controller for Stand-Alone Four-Leg Voltage Source Inverter
    Di Benedetto, Marco
    Lidozzi, Alessandro
    Solero, Luca
    Tang, Mi
    Formentini, Andrea
    Zanchetta, Pericle
    2018 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2018, : 2265 - 2270
  • [8] Simultaneous voltage unbalance compensation and neutral-to-ground voltage minimization for an islanded mini-grid using model predictive control
    Ayoubi, Effat
    Miveh, Mohammad Reza
    Ghadimi, Ali Asghar
    Bagheri, Sajad
    ENERGY SCIENCE & ENGINEERING, 2022, 10 (09) : 3301 - 3316
  • [9] Impedance Emulation for Voltage Harmonic Compensation in PWM Stand-Alone Inverters
    Arricibita, David
    Sanchis, Pablo
    Gonzalez, Roberto
    Marroyo, Luis
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2017, 32 (04) : 1335 - 1344
  • [10] Sliding Mode Control of Three-Phase Four-Leg Inverters via State Feedback
    Yang, Long-Yue
    Liu, Jian-Hua
    Wang, Chong-Lin
    Du, Gui-Fu