Amount of heat available from a prosumer of a 5th generation district heating and cooling (5GDHC) system: Case study of a data center

被引:7
作者
Chicherin, Stanislav [1 ,2 ,3 ]
机构
[1] Vrije Univ Brussel VUB, Fac Engn, Thermo & Fluid Dynam FLOW, Pleinlaan 2, B-1050 Brussels, Belgium
[2] Vrije Univ Brussel VUB, Brussels Inst Thermal Fluid Syst & Clean Energy BR, B-1050 Brussels, Belgium
[3] Univ Libre Bruxelles ULB, B-1050 Brussels, Belgium
来源
JOURNAL OF BUILDING ENGINEERING | 2023年 / 76卷
关键词
Temperature; Chiller; Capacity; Fan; Design;
D O I
10.1016/j.jobe.2023.107138
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The research problem is no method to estimate the specifications of a data center when no design data is available. The aim is to check capacities and temperature levels to supply energy to a 5th generation district heating and cooling (5GDHC) system. The methodology includes studying satellite images and design documents of similar projects. Ventilation chambers, roof-top units (RTUs), dry coolers, and free cooling chillers are recognized on satellite images. We study the layout of the heating, ventilation, and air-conditioning (HVAC) system, technological limitations, and server and cooling loads. The results suggest excluding RTUs, adding adjusting factors to dry coolers, and investment costs for the conversion from air to water cooling. Chillers and fan coil units operate in partial load mode to ensure the reliability level. Waste heat varies, although server power consumption remains constant. The configuration to utilize the waste heat is suggested. It includes a separate free-cooling heat exchanger, which allows turning off the compressors when the outdoor temperature drops. Variable supply and return temperatures compensate for the variation in outdoor temperature. In summer, the return temperature is high enough to supply heat directly to the 5GDHC network. In winter, heat pump boosting is necessary; the preferable outdoor temperatures are 0-10 degrees C. The implication is that water cooling increases data center feasibility as a prosumer for 5GDHC. The novelty is a method to assess how much energy is possible to recuperate; specific energy consumption/production is justified. The value is the solution to further decarbonize the energy industry and increase energy efficiency is suggested.
引用
收藏
页数:14
相关论文
共 32 条
  • [1] Air Cooled Chiller, AIR COOL CHILL SYST
  • [2] Comparative analysis and optimization of the annual performance for a novel internet data center cooling system
    Anka, Selorm Kwaku
    Lamptey, Nicholas Boafo
    Choi, Jong Min
    [J]. JOURNAL OF BUILDING ENGINEERING, 2023, 67
  • [3] A new generation of district heating system with neighborhood-scale heat pumps and advanced pipes, a solution for future renewable-based energy systems
    Arabkoohsar, Ahmad
    Alsagri, Ali Sulaiman
    [J]. ENERGY, 2020, 193 : 735 - 746
  • [4] An experimental study of thermal performance of the radiant ceiling cooling in office building in Thailand
    Aryal, Ashmin
    Chaiwiwatworakul, Pipat
    Chirarattananon, Surapong
    [J]. ENERGY AND BUILDINGS, 2023, 283
  • [5] Field demonstration and implementation analysis of model predictive control in an office HVAC system
    Blum, David
    Wang, Zhe
    Weyandt, Chris
    Kim, Donghun
    Wetter, Michael
    Hong, Tianzhen
    Piette, Mary Ann
    [J]. APPLIED ENERGY, 2022, 318
  • [6] Deep reinforcement learning to optimise indoor temperature control and heating energy consumption in buildings
    Brandi, Silvio
    Piscitelli, Marco Savino
    Martellacci, Marco
    Capozzoli, Alfonso
    [J]. ENERGY AND BUILDINGS, 2020, 224
  • [7] Optimal design of a 5th generation district heating and cooling network based on seawater heat pumps
    Calise, Francesco
    Cappiello, Francesco Liberato
    Cimmino, Luca
    d'Accadia, Massimo Dentice
    Vicidomini, Maria
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2022, 267
  • [8] Integrating a heat pump into a 4th generation district heating (4GDH) system - Two-mode configuration inputting operational data
    Chicherin, Stanislav
    Zhuikov, Andrey
    Junussova, Lyazzat
    [J]. ENERGY AND BUILDINGS, 2022, 275
  • [9] Methodology for retrofitting energy in existing office buildings using building information modelling programs
    Danial, Christine Ezzat
    Mahmoud, Ayman Hassaan Ahmed
    Tawfik, Manal Yehia
    [J]. AIN SHAMS ENGINEERING JOURNAL, 2023, 14 (06)
  • [10] Data Processing and Storage Center on the Territory of the Republic of Tatarstan. (DPC 'Innopolis'), 2021, PROJ DOC